22
7-2 Stopping
1. Turn the breaker to
『
OFF
』
.
2 .Turn the slow-down switch to
『
ON
』
.
3. Keep the engine (cool down) for about 5 minutes.
4. Turn the starter switch to
『
STOP
』
.
5. After the engine stops, turn the fuel lever to
『
CLOSE
』
.
<
<
<
<
Caution
>
>
>
>
●
When the engine will not stop in spite of turning the starter switch to STOP, turn the fuel lever to CLOSE,
then the engine will stop in a few minutes. In this case, be sure to consult with our authorized distributor
or our service section and ask to repair.
8-1. Selection – Welding Cable
Select the cable in proper gauge, based on the allowable amperage and the length, per the table shown
below.
The welding capacity is to reduce if the small gauge or long cable is used.
<
<
<
<
Caution
>
>
>
>
●
Welding cables should be used unstrained. When the welding cable are used in swirl, the welding
capacity is to reduce
Size of Cable
(
Unit
:
mm
2
)
Return
Length
20m
30m
40m
60m
80m
100m
Current
300A
30
38
50
80
100
125
250A
22
30
38
60
80
100
200A
22
30
30
50
60
80
150A
22
22
22
38
50
60
100A
22
22
22
30
30
38
8. Welding Operation