17 

(2) Circuit Breaker 

This switch is for transmitting electrical power to the load side. Turn to ON position to 
output voltage to the output terminals. Output to the load side is cut off when there is a 
short circuit or overload on the load side. 

 

(3) 3-Phase Earth Leakage Relay 

When current leak occurs, it trips to stop power transmission to load. 

 

< Note > 

 Do not use this relay as the ON/OFF switch to the load. 

 

Voltage Regulator 

 
(1) Voltage Regulator 

This dial is for regulating voltage output by the generator.Turn the dial clockwise to 
increase the voltage and counterclockwise to decrease it. 

5-4.   Frequency change 

  CAUTION : PROPERTY DAMAGE 

 When changing the frequency, be sure to adjust the Frequency adjusut screw 

and change the Controller settings. 

 

Turn the Power Switch to ON position. 
Press the Stop Mode Button and "

" button together to enter the editor 

display. 

Press the "

" button or the "

" button to select the Alt Config. 

Press the "

" button or the "

" button to select the Default Config and press 

the "

" button. 

Press the "

" button or the "

" button to change frequency and press the 

"

" button. 

Press and hold the "

" button to save settings. 

 

< Note > 

 Check that no loads are connected before using the frequency selector switch. 

 Be sure to select "50Hz 400V" or "60Hz 440V". Contact distributor if you want to use 

"50Hz 200V" or "60Hz 220V".

 

 This switch is set to 50Hz when shipped from the factory.

 

5-5.  Fuel Piping Switch (3Way Fuel Valve) 

  CAUTION : FIRE

 

 

 Always make sure that the Power Switch is OFF position when working on 

piping. 

 Always be sure to wipe up any spilled fuel. 

 After working on the piping, check that there is no fuel leakage. 

Change the 3way fuel valve to switch to supply fuel from the external tank. In that case, 
the internal fuel tank is not used. 

 

(1) If using the internal fuel tank 

The 3

way fuel valve is turned to the “A” side when the generator is shipped from the 

factory. 
 

 

 

 

 

 

 

 

 

Summary of Contents for DG60MI

Page 1: ...rtical Water Cooled 4 Cycle Diesel Engine DG60MI 400M R X753 007 96 0 X753801 360 0 CAUTION Do not operate the Generator or any other appliance before you have read and understood the instructions for...

Page 2: ......

Page 3: ...ration Store this manual in a specified location where it will be secure and available for consulting at any time Order another copy from the authorized distributor where this generator was purchased...

Page 4: ...19 7 Load Connections 19 7 1 Load Cable Selection 19 7 2 Connecting Load Cables 20 7 3 Earth Leakage Relay and Grounding 22 8 Pre Operation Inspection 23 8 1 Checking Engine Oil 24 8 2 Checking Coola...

Page 5: ...arth There is always a danger of being electrocuted by short circuit Be sure to test generator s insulation resistance periodically Grounding should be made after the engine is stopped Whenever the Ea...

Page 6: ...unding components immediately after stopping the engine as they are still extremely hot Do not open the radiator cap immediately after stopping the engine to avoid sustaining burns from hot vapor Hot...

Page 7: ...ting output terminal connection and load power source are consistent Cable burnout can occur due to generated heat if the load current exceeds the allowable current of the cable The voltage drop betwe...

Page 8: ...icated locations Order labels using part number indicated in the parenthesis Injury Part no X505 007550 Electric shock Part no X505 007560 Caution gm spec LLC Part no X505 007840 Caution fire Part no...

Page 9: ...utput kW 48 3 57 8 PS 65 7 78 6 Rated speed min 1 1500 1800 Displacement L 4 329 Combustion system Direct Fuel Injection with Turbo Charger Cooling method Radiator Lubricating method Forced lubricatio...

Page 10: ...to 40 C Relative humidity 85 or less Elevation 300 m or less Power source for submerged pumps and similar civil engineering equipment Power source for lighting and similar equipment Power source for e...

Page 11: ...Fuel Filter Oil Level Gauge Battery Oil Drain Plug Coolant Drain Hose Radiator Inside Alternator Check Door Air Cleaner Fuel Drain Plug Engine Check Door External Tank Fuel Return Water Separator Exte...

Page 12: ...9 4 2 Operation Panel Part Names Circuit Breaker Controller Power Switch Hour Meter Voltage Regulator Earth Leakage Relay...

Page 13: ...3 Phase Output Terminal R 3 Phase Breaker 32A 3 Phase Output Terminal S 1 Phase Breaker 15A 3 Phase Output Terminal T 3 Phase Receptacle 3 Phase Output Terminal O 1 Phase Receptacle Earth Leakage Term...

Page 14: ...rms Manual Mode Button This button places the controller into its Manual Mode Refer to section 9 1 Initial Startup Pre Check 1 Manual Start Auto Mode Button This button places the controller into its...

Page 15: ...ar To exit sleep mode press any button on the controller Main screens Status Status Screen Contents Generator at Rest Engine is stopped Generator Available Engine is running Generator Locked Out It is...

Page 16: ...se Sequence No use Active Config Ph N voltage frequency voltage set in the Alt Config is displayed Mains Status Screen Contents Mains Voltage No use Mains Frequency No use Mains Phase Sequence No use...

Page 17: ...k door when the Power Switch is in the ON position It will cause injury by rotating parts such as cooling fans and fan belt Always turn the Power Switch to the OFF position and stop the engine then cl...

Page 18: ...it is insufficient Refer to section 8 2 Checking Coolant If the coolant is at the specified amount it is probable that the fan belt is loose or there is a coolant leak Wait for the engine to cool and...

Page 19: ...el Low If the amount of fuel is small Fuel Level Low appear on the Operation Display and the engine will be automatically stopped Check if there is a sufficient amount of fuel and add fuel insufficien...

Page 20: ...r to enter the editor display Press the button or the button to select the Alt Config Press the button or the button to select the Default Config and press the button Press the button or the button to...

Page 21: ...sons should ever be under a lifted generator CAUTION INJURY Always be sure to use lifting hooks when lifting up the generator and slowly lift it straight up Personnel performing lifting work must wear...

Page 22: ...ng that it will be installed on a flat hard and leveled surface Accordingly care must be taken as using under any other installation conditions can result in a fault or malfunction Do not place any ob...

Page 23: ...nnecting the load cable to the output terminal or receptacle Close the output terminal cover before operating Do not insert a pin wire or other metal object into the electrical outlet Do not touch the...

Page 24: ...t 3 phase load Receptacle load Total R S T CON1 kVA 50 60 22 2 23 0 50 60 kW 40 48 17 8 18 4 40 48 Note In use the receptacle please set by the voltage regulator below 415V For 1 phase load Terminal v...

Page 25: ...ped Whenever the Earth leakage relay is activated you should always repair the leaking place first of all The generator is provided with the earth leakage breaker relay to detect any leakage produced...

Page 26: ...y step of the above procedure to the end the device is out of order Consult with our authorized distributor or our engineering section and ask to repair 3 Earth leakage Relay has activated If the eart...

Page 27: ...r better 2 Engine Oil Viscosity Use a diesel engine oil with an appropriate viscosity corresponding to the ambient temperature refer to the table Relation of Viscosity Temperature Temp C 3 Engine Oil...

Page 28: ...a toxic substance Wear rubber gloves and other protective wear when handling If someone mistakenly ingests LLC induce vomiting immediately and seek medical care If LLC gets on skin or clothing wash wi...

Page 29: ...gine fuel level on the controller will only display the fuel level for the internal fuel tank Be sure to close the cap tightly after refueling Note Use Diesel fuel ASTM D975 No 2 D in the event ambien...

Page 30: ...flammable gas Check the fluid level and add distilled water until it reaches the upper level when the fluid level is near the lower level Check the terminals for looseness and tighten properly Note It...

Page 31: ...temperature or humidity or an area with a large amount of dust Do not open any doors during operation Operating with door open can negatively affect cooling effect resulting in an equipment malfuncti...

Page 32: ...Start Button is pressed preheating is automatically performed but preheating is skipped when the coolant temperature not less than 30 degrees Pre heating time depends on the coolant temperature Autom...

Page 33: ...indicators will illuminate but all indicator lights will turn off when the engine is started Press the Manual Mode Button Press the Start Button to start the engine Adjust frequency with the Frequency...

Page 34: ...Air bleeding device runs for up to 4 minutes Press the Manual Mode Button Press the Start Button and confirm the engine has started properly Note Start the engine and check that the air is completely...

Page 35: ...o warn the operator of the fault location by use of indicator lamps or the Operation Display Check the fault location when the engine is automatically stopped or an indicator lamp illminates to stop t...

Page 36: ...of 8 to 9 mm Set the fuel level of the external fuel tank from 0 to 3 m from the underside of this generator The fuel level of the external fuel tank being lower than this generator will result in po...

Page 37: ...e enough to prevent the fluid from spilling on the ground Dispose of oil fuel coolant LLC filter battery and other hazardous materials according to laws and regulations concerning industrial waste Con...

Page 38: ...rator element Replace Fuel filter element Replace Fuel tank Drain water Fuel tank Clean Check for leaks Fuel Oil Coolant Fuel Cooling Water Oil Hoses and Anti Vibration Rubber Replace Every 2 years Ai...

Page 39: ...shortly after starting the engine be sure to always check that there is no oil leakage 2 Replacing the Oil Filter First Time 50 hours Thereafter Every 400 hours Drain the engine oil Refer to section...

Page 40: ...t cleaning Element part no P828889 ISUZU part no Cleaning the air filter element If dry dust is adhering Blow comprgssed air from inside the element If carbon or oil is adhering Replace with new parts...

Page 41: ...ing to the O ring Be careful not to over tighten the drain plug and air bleeder plug After attaching be sure to always start the engine and check that there is no fuel leakage Always be sure to wipe u...

Page 42: ...1000 hours Set a container to catch spilled coolant Remove the radiator plate Remove the radiator cap Loosen the drain cock of the radiator and the drain plug of the engine After the coolant has been...

Page 43: ...un the unit at more than 70 of the rated output for about half an hour until the exhaust gas become mostly colorless The carbon will accumulate when the unit runs at less than 30 of rated output Note...

Page 44: ...in a dry and dust free location Also cover when storing so that rain cannot enter through the suction or exhaust ports Note Adjust the fluid of the removed battery to the appropriate level and recharg...

Page 45: ...t is weak 2 Battery is deteriorated 3 Battery terminal is OFF or loose 4 Battery terminal is corroded 5 Relay is defective 6 Starter motor is defective 7 Controller is defective 1 Check battery liquid...

Page 46: ...ective 4 Coolant temperature is too low 5 Engine thermostat is defective 1 Ask our distributor to repair 2 Drain water in water separator fuel filter or fuel tank 3 Ask our distributor to repair 4 War...

Page 47: ...e earth leakage location Controller does not turn on 1 Battery output is weak 2 Battery is deteriorated 3 Battery terminal is OFF or loose 4 Battery terminal is corroded 5 Fuse is blown 6 Disconnected...

Page 48: ...45 1 400 440V 13 Generator Circuit Diagram...

Page 49: ...46 2 200 220V...

Page 50: ...47 14 Engine Electrical Circuit Diagram...

Page 51: ......

Page 52: ...2019...

Reviews: