2. Installation and wiring 

 

2.1 Installation site (environmental conditions)                                            

 

 

     

 Caution 

Do not use in the following locations. Doing so could lead to equipment failure, damage or fire. 
• Places exposed to flammable or corrosive gases, oil mist, or excessive dust that could cause insulation to deteriorate 
• Places where ambient temperature may fall below -10°C or rise above 50°C 
• Places where ambient humidity may exceed 90% RH or places subject to condensation 
• Places subject to strong vibration or impact 
• Places near strong electric circuit or places subject to inductive interference 
• Places exposed to water dripping or direct sunlight 
• Places where altitude exceeds 2000 m 

 

Note 

Among environmental conditions, IEC60664 installation category II, pollution class 2. 

 

2.2 Installation                                                                                                                                                     

1) Cut a hole for mounting the indicator by referring to the cutout drawing in section 2.3. The panel thickness should be 1.0 – 4.0 mm. 
2) The indicator is provided with tabs for mounting. Insert as is from the front surface of the panel. 

Note 

SD24 indicators are panel mounted indicators. 
Be sure to mount on the panel. 

 

 

2.3 External dimensions and panel cutout                                                 

External dimensions 

 

 

 

 

 

 

 

   

  Unit: mm 

 

Panel cutout 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

   

  Unit: mm 

 
 

2.4 Wiring                                                                                                                                                                                     

 

     

 WARNING 

Do not supply power when wiring. Doing so could result in electrical shock. Be sure to ground the protective conductor terminal ( ). 
Failure to ground could result in electrical shock. After wiring, do not touch terminal elements or other charged parts while conducting 
electricity. 

DISP

3

4

MAX

MIN

SET

HOLD

Summary of Contents for SD24 Series

Page 1: ...al attention Safety precautions WARNING The SD24 Series digital indicators are designed to indicate temperature humidity and other physical amounts for general industrial equipment You should either t...

Page 2: ...quipment failure or fire Do not allow the draft holes to become clogged with dust etc Doing so could shorten the life of the product due to temperature rise or insulation deterioration and could resul...

Page 3: ...AL1 AL2 and AL3 AL4 are COM shared Contact capacity 240V AC 2A resistive load 4 Alarm output optional 2 Output 2 points AL1 AL2 contact c Contact capacity 240V AC 2 5A resistive load 00 Without 03 0...

Page 4: ...ude exceeds 2000 m Note Among environmental conditions IEC60664 installation category II pollution class 2 2 2 Installation 1 Cut a hole for mounting the indicator by referring to the cutout drawing i...

Page 5: ...agnetic induction noise For power supply use wiring or cable with sectional area of at least 1 mm that offers the same performance as 600V vinyl insulated wiring The ground wire should be at least 2 m...

Page 6: ...and mode 1 screen group Press and hold for approximately 2 seconds to switch from 0 0 to 1 0 screen group and vice versa Down key Decrements parameter values on the setting screens The decimal point o...

Page 7: ...eration for mode 0 screen group The mode 0 screen group consists of items that are used frequently during operation The main key operations are as follows Key operation for mode 1 and 2 screen group C...

Page 8: ...unication protocol 1 26 Communication address 1 27 Communication data 1 28 Start character 1 29 BCC operation 1 30 Communication speed 1 31 Delay time 1 32 1 22 Analog output Scaling higher limit DI1...

Page 9: ...Linear approximation A2 2 7 Linear approximation B2 2 8 Linear approximation A3 2 9 Linear approximation B3 2 10 Linear approximation A4 2 11 Linear approximation B4 2 12 Linear approximation A5 2 13...

Page 10: ...7 1 Latching function for alarm output KEEP Latch RSET Unlatch KEEP RSET KEEP 0 3 Alarm 3 unlatching Indicates alarm 3 status Can be unlatched Sets alarm 3 code to type with latching function screen 1...

Page 11: ...lower limit value with latching function Note Screen is not displayed when alarm 4 code screen 1 17 is non none or in the case of So scale over See 8 Specifications Setting Range Refer to initial valu...

Page 12: ...dHi_L Deviation higher limit value with latching function dLo_L Deviation lower limit value with latching function dHL_L Deviation higher lower limit value with latching function Note Setting contents...

Page 13: ...Inverse scaling is possible The same value cannot be set for both higher limit value and lower limit value screen 1 22 Measuring range lower limit value higher limit value Lower limit value 1 22 Analo...

Page 14: ...EP rAm r_E EEP 5 5 Mode 2 screen group 2 0 Mode 2 initial screen First screen of the mode 2 screen group 2 1 Power frequency Sets displays power frequency Note Does not have to be set under ordinary c...

Page 15: ...is OFF 5 00 105 00 0 00 2 18 Linear approximation B7 Sets displays linear approximation B7 Note Not displayed when linear approximation screen 2 4 is OFF 5 00 105 00 0 00 2 19 Linear approximation A8...

Page 16: ...the power is turned off The value when the power is turned back on is then held Note The hold value display is maintained even if the device displays an error message during hold Alarm output is in a...

Page 17: ...larm 9999 19999 9999 unit dHL Deviation higher lower limit value alarm 1 19999 19999 unit dHi_L Deviation higher limit value alarm with latching function 9999 19999 19999 unit dLo_L Deviation lower li...

Page 18: ...alarm type is set to HA With standby action the alarm is not output while the power is on even if alarm output conditions are satisfied The alarm is output when the value re enters the alarm range aft...

Page 19: ...range is 0 0 5 0 of PV input range 7 4 10 segment linear approximation Enabling 10 segment linear approximation Set only for voltage or current input Ineffective during inverse scaling Function that...

Page 20: ...power supply 24V DC 50 mA and can use it in combination with humidity sensor H71 and TH71 Series For voltage V input connection For current mA input connection 7 8 9 10 TC RTD A B B 7 10 9 22 21 24V D...

Page 21: ...T N U L DIN43710 WRe5 26 For details see 8 Specifications Measuring Range Codes Lead wire tolerable resistance 100 max Input resistance 500k min Burnout function Standard feature up scale Cold juncti...

Page 22: ...1 19999 19999 unit Control input DI Number of input points 2 points Type of DI allocation Selected for each DI from among the following 4 types Not assigned HLD Hold Maintains current input value RESE...

Page 23: ...0 0 0 600 0 0 0 1000 0 0 00 120 00 300 0 900 0 150 0 200 0 150 0 600 0 80 00 100 00 60 00 120 00 40 00 140 00 0 00 180 00 0 00 80 00 0 00 200 00 0 0 400 0 0 0 600 0 0 0 600 0 0 0 900 0 0 00 120 00 0 0...

Page 24: ...sistance 500V DC 20M min between all input output terminals and power terminals 500V DC 20M min between all input output terminals and ground terminals Dielectric strength 2300V AC between all input o...

Reviews: