12
1-7 Input scaling higher limit value
Sets/displays scaling higher limit value for
voltage/current input.
Note
In case other than voltage/current input (Thermocouple and R.T.D. input)
only displays scaling higher limit value. Span between lower and higher
limit values is 10 – 40,000.
Inverse scaling is possible.
-9999 – 30000 unit
10000 unit
1-8 Alarm 1 code
Sets/displays type of alarm 1 action.
For details on various types of action, see 7.1
Types of action for alarm output.
non
:
None
HA
:
Higher limit absolute value
LA
:
Lower limit absolute value
HA_L
:
Higher limit absolute value
(with latching function)
LA_L
:
Lower limit absolute value
(with latching function)
So
:
Scaleover
Note
If alarm code is modified, hysteresis, standby action and alarm setting
value are reset. The values are however not reset if HA is changed to
HA_L or vice versa, or LA is changed to LA_L or vice versa.
non, HA, LA, HA_L, LA_L, So
HA
1-9 Alarm 1 hysteresis
Sets/displays alarm hysteresis.
Note
Screen is not displayed when alarm 1 code (screen 1-8) is non or in the
case of So.
1 – 9999 unit
20 unit
1-10 Alarm 1 standby action
Sets/displays type of alarm 1 standby action.
Note
Screen is not displayed when alarm 1 code (screen 1-8) is non or in the
case of So.
OFF, ON
OFF
1-11 Alarm 2 code
Sets/displays type of alarm 2 action.
For details on various types of action, see 7.1
Types of action for alarm output.
non :
None
HA
: Higher limit absolute value
LA
: Lower limit absolute value
HA_L : Higher limit absolute value
(with latching function)
LA_L
: Lower limit absolute value
(with latching function)
So :
Scaleover
The following are not displayed when alarm
code is non or So.
dHi
: Deviation higher limit value
dLo
: Deviation lower limit value
dHL
: Deviation higher/lower limit value
dHi_L
: Deviation higher limit value
(with latching function)
dLo_L
: Deviation lower limit value
(with latching function)
dHL_L
: Deviation higher/lower limit value
(with latching function)
Note
Setting contents are initialized if alarm code is modified. The values are
however not initialized if HA is changed to HA_L, LA is changed to LA_L,
dHi is changed to dHi_L, dLo is changed to dLo_L, dHL is changed to
dHL_L or vice versa. The deviation setting is the value relative to alarm 1.
non, HA, LA, HA_L, LA_L, So
dHi, dLo, dHL, dHi_L, dLo_L,
dHL_L
LA
1-12 Alarm 2 hysteresis
Sets/displays alarm 2 hysteresis.
Note
Screen is not displayed when alarm 2 code (screen 1-11) is non or in the
case of So.
1 – 9999 unit
20 unit
1-13 Alarm 2 standby action
Sets/displays type of alarm 2 standby action.
Note
Screen is not displayed when alarm 2 code (screen 1-11) is non or in the
case of So.
OFF, ON
OFF
1-14 Alarm 3 code
This screen is not displayed when contact c
alarm is selected.
Sets/displays type of alarm 3 action.
For details on various types of action, see 7.1
Types of action for alarm output.
non
:
None
HA
:
Higher limit absolute value
LA
:
Lower limit absolute value
HA_L
:
Higher limit absolute value
(with latching function)
LA_L
:
Lower limit absolute value
(with latching function)
So
:
Scaleover
Note
Setting contents are reset if alarm code is modified. The values are
however not reset if HA is changed to HA_L or vice versa, or LA is
changed to LA_L or vice versa.
non, HA, LA, HA_L, LA_L, So
non
1-15 Alarm 3 hysteresis
This screen is not displayed when contact c
alarm is selected.
Sets/displays alarm 3 hysteresis.
Note
Screen is not displayed when alarm 3 code (screen 1-14) is non or in
the case of So.
1 – 9999 unit
20 unit
1-16 Alarm 3 standby action
This screen is not displayed when contact c
alarm is selected.
Sets/displays type of alarm 3 standby action.
Note
Screen is not displayed when alarm 3 code (screen 1-14) is non or in the
case of So.
OFF, ON
OFF
mV
V
mA