51
4. Parameter description
Parameter
4.10
JOG Mode (P.15, P.16)
P.15 “JOG frequency”
P.16 “JOG acceleration/deceleration
time”
Related parameters
P.20 “Acceleration/deceleration
reference frequency”
P.21
“
Acceleration/deceleration
time increments
”
● In JOG mode, the output frequency is the set value of P.15, and the acceleration/deceleration time
is the set value of P.16.
Parameter
Factory setting
Setting range
Remarks
15
5Hz
0~400Hz (Note 2)
---
16
0.5s
0~360s
When P.21=0
0~3600s
When P.21=1
P.16
P.20
P.15
P.15
P.20
P.16
Running
forward
Running
backward
Press
FWD
Press
REV
Output frequency
Time
Note: 1. Please refer to Section 3-1 for how to enter the JOG mode.
2. If P.187=1, P.15 is in the range of 0~1000Hz.
4.11 Input Signal across Terminal 4-5 Selection Function (P.17)
P.17 “Input signal across terminal 4-5 selection”
●
SE2
series inverters have two analog input channels, terminal 2-5 and terminal 4-5. Only voltage
signal can enter across terminal 2-5, but both voltage signal and current signal can enter across
terminal 4-5, which is switched by P.17.
Parameter
Factory setting
Setting range
Remarks
17
0
0~1
0
Current signal valid
1
Voltage signal valid