background image

User Manual

 

ATC-3001 1-port Modbus Gateway

 

 

 

Copyright 

©

 2011

 

SHENZHEN ATC TECHNOLOGY CO., LTD.   

6

 

 

 

 

3.2 Configuration by Telnet Utility  

 

One can use Telnet utility to change configuration settings of ATC-3001 by following steps

 

3.2.1 Login to the System 

Open Ms-DOS command prompt window 

Telnet  to  ATC-3001  using  command 

Telnet  IP_address

.(  For  example

Input

  Telnet  10.0.50.100

  in 

Ms-DOS  command  prompt  window).After  telnet  to  ATC-3001,  system  prompts  for  a  password,  the  default 
password is left it blank. (Figure 3.4) 

 

Figure 3.4 Login to the system 

 

Note:

 One can press the default button of ATC-3001 to reset the password to the default value. 

 

1.  After verifying the password, the following terminal screen appears.( Figure 3.5) 

 

Figure 3.5 Main menu 

 

Note: 

Changes to networking parameters will take effect only when one exit and restart ATC-3001. 

 

->

Select 

1

  from 

Input  choice  and  enter  (1~8,a~f):

  to  enter  show  configuration  page  as 

following:( Figure 3.6) 

Summary of Contents for ATC-3001

Page 1: ...Model ATC 3001 1 port Modbus Gateway User s Manual Updated on 2011 01 11 Tel 86 755 8345 3318 Fax 86 755 8355 5891 http www szatc com...

Page 2: ...transmitted stored in a retrieval system or translated into any human or computer language in any form by any means in whole or in part without the prior express written consent of SHENZHEN ATC TECHN...

Page 3: ...2 Configuration by Telnet Utility 6 3 2 1 Login to the System 6 3 2 2 IP Setup 7 3 2 3 Gateway Setup 7 3 2 4 Subnet Mask Setup 7 3 2 5 COM1 Setup 7 3 2 6 Exit with Save and Reset 8 3 2 7 Exit with Sav...

Page 4: ...3 1 Device Search 20 A 3 2 Firmware 23 A 3 3 Configuration 24 A 3 4 About 26 Appendix B Specifications 28 B 1 Hardware Specifications 28 B 2 Software Specifications 29 B 3 Panel Layout and Connector...

Page 5: ...Hardware Infrastructure Modbus Gateway supports the four most commonly used hardware communication interfaces RS232 RS485 RS422 and Ethernet The simple to use configuration software provided with Modb...

Page 6: ...Data is transmitting on Ethernet for 100Mbps Blinking with Orange Data is transmitting on Ethernet for 10Mbps Table 1 LAN LED Message 2 1 2 COM Port LED Message Description Off No data is transmitting...

Page 7: ...nnect ATC 3001 to Ethernet network Use a standard straight through Ethernet cable when one connect it to a hub switch one also can connect it to ones PC s Ethernet port via a cross over Ethernet cable...

Page 8: ...admin Password Null leave it blank COM 1 9600 None 8 1 No flow control buffer disabled packet delimiter timer 2ms Modbus Type Listen port 502 SysName of SNMP name SysLocation of SNMP location SysCont...

Page 9: ...HCP function By default the DHCP function on ATC 3001 is disabled one can use Device View software to search network information automatically by following steps Execute Device View Figure 3 1 Click o...

Page 10: ...100 in Ms DOS command prompt window After telnet to ATC 3001 system prompts for a password the default password is left it blank Figure 3 4 Figure 3 4 Login to the system Note One can press the defaul...

Page 11: ...2 2 IP Setup Select 2 from Input choice and enter 1 8 a f to Setup IP Figure 3 7 Figure 3 7 IP Setup 3 2 3 Gateway Setup Select 3 from Input choice and enter 1 8 a f to Setup Gateway Figure 3 8 Figure...

Page 12: ...Reset Select 7 from Input choice and enter 1 8 a f to Exit with Save Please choose this option to save all the previous changes to EEPROM the device will restart automatically 3 2 7 Exit with Save an...

Page 13: ...default empty password to 1111 Figure 3 12 change the password 2 If one want to change the password please type the old password in the Please input old password field type the new password in the Ple...

Page 14: ...default password is null leave it blank 3 ATC 3001 s network link mode and COM ports settings can be configured in different web pages 4 Click Save Configuration to save settings 5 Click Restart butto...

Page 15: ...in the Old Password field input the new password in the New Password and the Verified Password fields and then click on Save Configuration to update the password Note One can press the default key of...

Page 16: ...ormation Enable SNMP by checking Enable fill in network identification information under SNMP field and click on the Save Configuration button to save the changes please notice that the setting will n...

Page 17: ...to 0 Auto ATC 3001 will automatically chooses the optimal delimiter according to the baud rate 3 The COM Type Selection will show different port interface according to its selected port type 4 After...

Page 18: ...Assign a New IP Address by ARP Command Use ARP command to assign a static IP address of ATC 3001 using its hardware MAC address The MAC address is printed on the rear side of device in the format of...

Page 19: ...User Manual ATC 3001 1 port Modbus Gateway Copyright 2011 SHENZHEN ATC TECHNOLOGY CO LTD 15 Figure 3 21 Assigning a new IP address by ARP command...

Page 20: ...k management tool from NetworkView Software Inc www networkview com It discovers all TCP IP nodes in a network using DNS SNMP and ports information and documents with printed maps and reports for futu...

Page 21: ...isplay information about the device including IP Address Company SysLocation Max 15 characters SysName Max 9 characters and types etc Figure 4 4 Figure 4 4 NetworkView display device information Note...

Page 22: ...Server IP address If the connection is established the Reply messages are displayed otherwise it will indicate Request timed out Figure 5 1 Figure 5 1 Standard TCP IP utility ping command 5 2 Use Dev...

Page 23: ...User Manual ATC 3001 1 port Modbus Gateway Copyright 2011 SHENZHEN ATC TECHNOLOGY CO LTD 19 Figure 5 2 DeviceView configuration Utility...

Page 24: ...Field Description IP conflict There are two devices with the same IP address in the network The device is using DHCP The device is being located You have logged into the device MAC conflict There are...

Page 25: ...TC TECHNOLOGY CO LTD 21 Alternatively users can select by clicking the button on the toolbar as below Broadcast Search Once Broadcast Search is selected a box will pop up as below The user may type in...

Page 26: ...ed an interface will pop up as below Here user may have two options Select an IP address to search or Search device in the range of IP address Search by MAC Address If Search by MAC Address is selecte...

Page 27: ...all re search devices by using the current search way A 3 2 Firmware This function is applied to downloading a firmware into the selected device The user can enter the window for downloading by firstl...

Page 28: ...them by selecting Apply for all selected devices have same model A 3 3 Configuration This function is for device configuration to set up parameters to import and to export the parameters and to set up...

Page 29: ...to locate a device when its IP address is known but its position is unknown If a device is selected the device will appear to sing Users can locate the device by selecting the Configuration submenu Lo...

Page 30: ...er setting directly through the submenu option Config by Browser and a Web browser is shown in the figure below Options The option is mainly applied to setting some common working rules of DeviceView...

Page 31: ...User Manual ATC 3001 1 port Modbus Gateway Copyright 2011 SHENZHEN ATC TECHNOLOGY CO LTD 27...

Page 32: ...ld 4 75V SerialPort Communication One RS 232 and one RS 485 RS 422 selectable RS 232 EIA RS 232C standard Full Duplex DB9 RS 485 2 4 wires Half Full duplex Terminal Block RS 422 4 wires Half Full dupl...

Page 33: ...buffer size 16K bytes RS 232 or RS 485 RS 422 receiving buffer size 4K bytes RS 232 or RS 485 RS 422 transmitting buffer size 4K bytes B 3 Panel Layout and Connector Pin Assignments B 3 1 Pin Assignm...

Page 34: ...5 Blue White Blue White Pin6 Orange Green Pin7 Brown White Brown White Pin8 Brown Brown One can choose either 568A or 568B definition If one want to make a crossover cable one should use 568A and 568B...

Page 35: ...Data is transmitting on COM port Table 2 COM Port LED Message B 4 3 RUN LED Message Description LED on R1 are shorted to disable AP firmware running LED blinking rate 0 5Sec AP firmware is running nor...

Page 36: ...DeviceView program to verify their availability 2 Prepare the download tool and press any key to edit its configuration file dapdl cfg dapdl cfg file can be found in the product CD 3 Edit the dapdl cf...

Page 37: ...stem remains intact 2 If ATC 3001 does not receive any upgrading data within 30 seconds ATC 3001 will restart automatically and the system remains intact 3 After the upgrading process finishes ATC 300...

Page 38: ...cur during the process Error Cause Message Comments Illegal Hex file format Hex File Text Error Hex File Check Sum Error Hex File Format Error Hex File End of Record Error ATC 3001 handshaking problem...

Page 39: ...is used in the situation that one downloaded a wrong version of firmware that caused the system crashed To disable the current version of firmware and prevent it from executing please do the followin...

Page 40: ...32 422 485 software selectable ATC 3001 Ports 1 port DB9 and 1 port TB6 Baud Rate 1200bps to 230Kbps Parity None Odd Even Mark Space Data Bits 7 or 8 Stop Bits 1 or 2 Data Packet Delimiter 0 to 30000...

Page 41: ...HENZHEN ATC TECHNOLOGY CO LTD 37 Ordering Information ATC 3000 TCP IP to RS 232 RS 422 RS 485 converter ATC 3001 1 port Modbus Gateway Optional Accessories Power Adapter US315 12 US EU AC100 240V DC 9...

Reviews: