Shel lab SMO5CR-2 Installation And Operational Manual Download Page 8

8

 

MODEL SMO5CR-2 (CR1-2) CLEAN 
ROOM READY INSTRUCTIONS 

This  oven  has  been  designed  to  operate  at  class  100  standards.  It  is  not  shipped  clean  room 
ready and the instructions below must be followed for proper installation. 

See Figure 2

 

6.1 

BURN-IN OF THE HEPA FILTER 

Before using this oven, it is important that the filter be burnt-in properly.  During burn-in, 
the Hepa filter will off gas.  Because of this the intake and exhaust ports must be open, 
with the exhaust ports being ducted outside.  A material safety data sheet is included with 
your operation literature for reference.  Note that you should read Section 7.0 and have a 
clear understanding of how to operate the unit prior to following this procedure. 

A. 

To burn in filter: 

1. 

Set oven at:  125

C for 1 hour; 

150

C for 4 hours; 

175

C for 1 hour; 

200

C for 1 hour. 

2. 

If operating temperature is higher than 200

C, continue the cycle of one 

hour at 25

 increments until the operating temperature is achieved. 

B. 

After burn-in, the interior must be disassembled and cleaned.  Make sure unit is 
unplugged  and  cooled  down  before  disassembly.    When  disassembling,  use  an 
8/32  nut  driver  for  removing  all  the  cap  nuts.    Remove  the  bottom  liner  insert 
before removing the liner side inserts.  Do not remove the Hepa filter cover.  After 
burn-in, the filter is very delicate (like the mantel of a lantern) and  will fall  apart.  
The casing should only be removed when replacing the filter. 

6.2 

CONTROL AREA EXHAUST 

As  part  of  this  design  the  control  compartment  is  sealed  and  requires  a  minimum  of  30 
CFM  (Cubic  Feet  Per  Minute)  to  be  drawn  from  the  control  compartment  exhaust  port.  
This  is  required  to  limit  the  control  compartment  temperature  and  maintain  Class  100 
integrity.    If  you  are  unable  to  exhaust  the  minimum  30  CFM  from  the  control 
compartment,  then  you  must  limit  the  maximum  operating  temperature  to  200

C.  

Operation  of  the  unit  above  200

C,  without  moving  the  required  30  CFM  through  the 

control compartments exhaust, will result in control degradation and process failure.  Not 
supplying  the  required  30  CFM  may  also  keep  the  unit  from  operating  at  class  100 
specifications  by  allowing  particulars  from  the  control  compartment  to  escape  into  the 
room.  

Section 

Summary of Contents for SMO5CR-2

Page 1: ...Previously Designated as CR1 2 INSTALLATION AND OPERATIONAL MANUAL 01 2013 4861580 P O Box 627 300 N 26th Avenue Cornelius Oregon 97113 EMAIL tech Shellab com INTERNET http www Shellab com 1 800 322...

Page 2: ...NCE SECTION 9 0 TROUBLESHOOTING AND SERVICE SECTION 10 0 PARTS LIST UNIT SPECIFICATIONS SCHEMATICS This unit is a special purpose oven for professional industrial or educational use where the preparat...

Page 3: ...and enter your claim on the form supplied by the carrier 1 2 Inspect for concealed loss or damage on the unit itself both interior and exterior If necessary the carrier will arrange for official inspe...

Page 4: ...you should consult your manual for further description or discussion of a control or user item 2 2 Indicates Adjustable Temperature 2 3 Indicates AC Power ON 2 4 Indicates High Limit Safety 2 5 Indic...

Page 5: ...c Avoid direct sun fast moving air currents heating cooling ducts and high traffic areas Allow a minimum of 30 cm between the unit and walls or partitions which might obstruct free air flow 3 3 Liftin...

Page 6: ...own set point preventing sample loss or unit degradation Please note that it is not recommended that the unit be allowed to operate using only the High Limit to control temperature as temperature unif...

Page 7: ...ealt with according to local regulations Your dealer can provide you with a power exhaust which greatly helps under these applications 5 3 Do not operate near noxious fumes 5 4 Do not place sealed or...

Page 8: ...mbled and cleaned Make sure unit is unplugged and cooled down before disassembly When disassembling use an 8 32 nut driver for removing all the cap nuts Remove the bottom liner insert before removing...

Page 9: ...9 Figure 2...

Page 10: ...Once the down arrow has been pushed use the up and down arrow to achieve desired set point 3 After reaching desired set point the display should blink once to enter the value 4 To Auto Tune push the u...

Page 11: ...C in 30 minutes and control for 1 hour at 100 C Then you want to ramp up to 150 in 30 Minutes and control for 2 hours Then you want to cool down to start Set Point with Power Exhaust Outlet activated...

Page 12: ...and the display should read SENS This enters you in the Input Configuration Menu To navigate through the menu press the up and down arrows Press the up or down arrow repeatedly until you reach OFFS in...

Page 13: ...en cleaning and assure all volatile or flammable cleaners are evaporated and dry before reattaching the unit to the power supply 8 2 Storage If the oven is to be turned off it can be reactivated witho...

Page 14: ...irm with front panel lights that controller is calling for heat 7 high limit failure confirm with front panel lights that High Limit is operating correctly 8 wiring problem check all functions and com...

Page 15: ...problem solved then follow instructions in Section 7 5 for correct setting 8 electrical noise remove nearby sources of RFI including motors arcing relays or radio transmitters 9 bad connection on tem...

Page 16: ...other loads are on the wall circuit Unit will not turn on 1 check wall power source 2 check fuse circuit breaker on unit or in wall 3 see if unit is on e g fan or heater and just controller is off 4...

Page 17: ...inlet 2800503 Heating Element 9570831 Hepa filter 9990503 High Limit Controller 1750571 High Limit Indicator Pilot Lamp 4650553 Leveling Feet 2700512 Main Temperature Controller 1750803 ON OFF Switch...

Page 18: ...5 lbs Dimensions Exterior WxDxH in Interior WxDxH in SMO5CR 2 CR1 2 35 x 30 25 x 38 17 x 20 x 20 125 Capacity Cubic Feet SMO5CR 2 CR1 2 4 0 Temperature Range Uniformity Control SMO5CR 2 CR1 2 Amb 15 t...

Page 19: ...19 WIRE DIAGRAM...

Page 20: ...includes components not manufactured by Manufacturer is not covered by this warranty Any alteration or removal of the serial number on Manufacturer s parts will void this warranty Under no circumstanc...

Reviews: