background image

SIM02E-013 

 

4

The approved way to mount SHARP PV modules to a support 
structure is described in this INSTALLATION MANUAL. 
Although SHARP does not specify or warrant frame clamps or 
clips, using frame clamps (not provided) or clips (not provided) 
is  possible  when  they  are  designed  for  PV  modules  and  with 
minimum  dimensions  on  the  sides  of  the  PV  module  in 
accordance with the instructions and drawings provided. If using 
frame clamps or clips, the PV modules should be fixed rigidly 
and there shall be no damage to the PV modules by deforming 
mounting structure against design load. 
The  SHARP  PV  module  guaranty  may  be  void  if  customer-
selected  frame  clamps  are  improper  or  inadequate  for  PV 
module properties (including strength or material) or installation. 
Note  that  if  metal  clamps  are  used,  there  must  be  a  path  to 
ground from the clamps, (for instance, using star washers in the 
clamp  hardware  set).Please  review  the  descriptions  and 
drawings carefully; not mounting the PV modules according to 
one of these methods may void your guaranty. The PV module 
has  passed  the  test  sequence  which  contains  3  cycles  each 
performed at 5,400 Pa positive and 2,400 Pa negative loading 
in accordance with IEC61215-2. The system designer shall be 
responsible to ensure protective structures so that the module 
can bear to the loads that are different from the test condition 
defined in the IEC standard. 
Support structures that PV modules are mounted on should be 
rigid.  SHARP  PV  modules  are  designed  to  ensure  optimal 
electrical  performance  under  the  condition  that  they  are 

mounted  on  rigid  support  structures.  Deformation  of  support 
structure may damage PV module with its electric performance. 
When  mounting  the  PV  module  on  structure,  ensure  that  no 
corner has a displacement of more than 2 mm per every 1,000 
mm of the diagonal.

 

The mounting structure shall enable the PV 

module  to  deflect  freely  under  wind  and/or  snow  load  not  to 
make direct impact to the center of the PV module.(i.e. min.10 
cm from the roof surface to the bottom face of PV module frame). 
The  installer  shall  be  responsible  for  the  selection  and 
construction of support structure. 

 

9. MAINTENANCE 

The PV modules are designed for long life and require very little 
maintenance.  If  the  angle  of  the  PV  module  is  5  degrees  or 
more, normal rainfall is sufficient to keep the PV module glass 
surface  clean  under  most  weather  conditions.  If  dirt  build-up 
becomes excessive, use only a soft, damp cloth and water to 
clean  the  glass.  If  cleaning  the  back  of  the  PV  module  is 
required,  take  utmost  care  not  to  damage  the  back  side 
materials. In order to ensure the operation of the system, check 
the  connection  of  wiring  and  the  state  of  the  jacket  of  wires 
occasionally. 
The PV modules is equipped with anti-reflective coating glass, 
do  not  touch  the  glass  since  finger  prints  or  stains  will  easily 
mark.  If  dirt  build-up  becomes  excessive,  clean  the  glass 
surface with water only. 
 

 

INSTALLATION INSTRUCTIONS -PHOTOVOLTAIC MODULES-

 
1. INSTALLATION 
Mounting Using Clamps: 

The PV modules can be mounted with clamps (clips) as defined 
in the following. Note that the mounting clamps should meet the 
required  dimensions  as  defined  in  the  Figure1.  Note  that  the 

CLAMP CENTER POSITION (e, L, S)

 from the module corner 

should  be  located  in  the  range  as  specified  in  the  Annex.  All 
clamps shall hold the module frame completely within their width. 
Please be aware that the module under heavy load would get 
serious  deflection  which  could  cause  cell  cracks  that  affects 
power degradation. The PV module must be supported on the 
array system and must overlap the array rail by at least 10mm. 
 

Mounting Using Frame Bolt Holes: 

The modules may be fastened to a support using the bolt holes 
in the bottom of the frames at any of locations shown in Annex. 
The  module  should  be  fastened  with  four  (4)  M8  bolts. 
Recommended torque is 12.5 Nm. 
 

2. ELECTRICAL INSTALLATION INSTRUCTION 
Cable characteristics 

Conductor  size:  4.0  mm

2

,  Cable  type:  H1Z2Z2-K  or  62930 

IEC131 
Maximum DC voltage: 1.5 kV 
Ambient temperature: -40 °C to +90 °C 
Maximum conductor temperature: 120 °C 

 
 
 
 
 
 
 

 
 

PV module configuration (Recommend) 

# Maximum series configuration: please refer to Table 1 
# Maximum parallel configuration: (Parallel connection of each 
string shall be conducted with following two options. Any other 
parallel connections are prohibited.) 
a)  Case  of  using  the  diodes;  1  diode  per  maximum  2  parallel 

strings (Connect a diode or more in series for every string or 
every  2  parallel  strings  for  protection  of  PV  module  from 
reverse current over load.) 

b) Case of using the fuses; 1 fuse per every string (Connect a 

fuse for every single string for protection of PV module from 
reverse current over load.) 

 

Connection cables requirement 

The PV module shall be mated to the same connectors; 
Type: MC4 (System voltage 1,000V) 
Brand: Staubli Electrical Connectors  
 
In  case  connectors  will  be  replaced  by  qualified  personnel 
according the mounting instructions of the manufacturer of the 
new connectors, the guarantees on the module itself, will remain 
valid according the applicable terms. 
 

3. WARNING 

Keep  all  PV  MODULES  and  electrical 
CONNECTORS 

clean 

dry 

before 

installation. 
 

4. Disposal

 

Dispose 

PV 

modules 

properly. 

For 

Information  about  the  proper  disposal, 
contact your local recycling site. 
 
 
 
 
 
 
 
 
 
 
 

Figure1. Clamps (Clips) requirement 
   1) Clamp: Al alloy, 3 mm Min. thickness 
   2) Catch length (50 mm Min.) 
   3) Covering depth (7 mm Min. on the frame) 
   4) Supporting depth (10 mm Min.) 
   5) Frame (applicable to all frame sections) 
   6) Array rail (applicable to parallel or crossed 
mounting) 

Summary of Contents for NU-JC415

Page 1: ...ures e g snow stopper to avoid possible damage 13 Periodically remove any overhanging snow and or ice from the PV module framework as it may cause deformation of the PV module frame GENERAL INSTRUCTIONS 1 INTRODUCTION This INSTALLATION MANUAL contains essential information for the electrical and mechanical installation that you must know before installing SHARP PV modules This also contains safety...

Page 2: ...ers and circuit breakers immediately should a problem occur 17 In case the glass surface of a PV module is broken wear goggles and tape the glass to keep the broken pieces in place 18 A defective PV module may generate power even if it is removed from the system It may be dangerous to handle the PV module while exposed to sunlight Place a defective PV module in a carton so PV cells are completely ...

Page 3: ...aximum output power when it faces the sun directly 5 degrees or more is recommended for the tilt angle of the PV module for the maintenance See 9 Maintenance For the standalone systems with a battery where the PV modules are attached to a permanent structure the tilt angle of the PV modules should be determined to optimize the performance when the sunlight is the scarcest In general if the electri...

Page 4: ...of wiring and the state of the jacket of wires occasionally The PV modules is equipped with anti reflective coating glass do not touch the glass since finger prints or stains will easily mark If dirt build up becomes excessive clean the glass surface with water only INSTALLATION INSTRUCTIONS PHOTOVOLTAIC MODULES 1 INSTALLATION Mounting Using Clamps The PV modules can be mounted with clamps clips a...

Page 5: ...calculated under the condition of Voc at 40 C Under normal conditions a PV module is likely to experience conditions that produce more current and or voltage than reported at Standard Test Conditions Accordingly the values of Isc and Voc marked on this PV module should be multiplied by a factor of 1 25 when determining component voltage ratings conductor current ratings fuse sizes and size of cont...

Page 6: ...teel Material Stainless steel Diameter M8 8 2 15 4 mm Diameter M8 8 5 15 5 mm Thickness 2 mm reference value Thickness 1 6 mm reference value 3 Bolt 4 Nut Material Stainless steel Material Stainless steel Size M8 Size M8 Diameter M8 x 20 mm Fig B1 The components for BOLT NUT ...

Reviews: