background image

SIM02E-013 

 

3

if the terminals of PV module are wet. 

12.  Do not touch the junction box and the end of output cables, 

the  cable  ends  (connectors)  ,  with  bare  hands  during 
installation or under sunlight, regardless of whether the PV 
module is connected to or disconnected from the system. 

13.  Do  not  unplug  the  connector  if  the  system  circuit  is 

connected to a load. 

14.  Do not stomp on the glass at work. There is a risk of injury 

or electric shock if glass is broken. 

15.  Do not work  alone  (always work  as a team of 2 or more 

people). 

16.  Do not damage the back sheet of PV modules when setting 

the mounting and/or equipotential bonding by bolts. 

17.  Do not damage the surrounding PV modules or mounting 

structure when replacing a PV module. 

18.  Bind  cables  by  the  insulation  locks.  Drooping  down  of 

cables from the junction box could possibly cause various 
problems  such  as  animal  biting,  electricity  leakage  in 
puddle. 

19.  Take  proper  measures  for  preventing  the  laminate 

(consisted  of  resin,  cells,  glass,  back  sheet,  etc.)  from 
dropping out of the frame in case the glass is broken. 

20.  Plastic components such as cables or connectors shall be 

located so that they will not be exposed to direct sunlight 
after installation to prevent degradation of them.

 

21.  If  batteries  are  used  with  PV  modules,  follow  safety 

precautions of the battery manufacturer.

 

22.  In case of extreme snow build-up, the weight of the snow 

may  cause  the  PV  module’s  frame  to  deform.  Take 
appropriate preventive measures to minimize any possible 
resulting damage. 

 

4. SITE SELECTION

 

In most applications, the PV modules should be installed in a 
location where there is no shading throughout the year. In the 
Northern  Hemisphere,  the  PV  modules  should  typically  face 
south, and in the Southern Hemisphere, the PV modules should 
typically face north. 
Please  make  sure  that  there  are  no  obstructions  in  the 
surroundings of the site of installation. TAKE PROPER STEPS 
in  order  to  maintain  reliability  and  safety,  in  case  the  PV 
modules  are  used  in  areas  such  as:  Heavy  snow  areas  / 
Extremely cold areas / Strong wind areas / Installations over, or 
near, water / Areas where installations are prone to salt water 
damage/corrosive  gas  environment/  Small  islands  or  desert 
areas. 
The results of the ammonia test and the salt-mist-corrosion test 
on the PV modules, carried out under such strict test conditions, 
should be disclosed for reference purposes only. The decision 
on  whether  the  PV  modules  are  suitable  and  compatible  for 
each installation field will depend on the user’s judgement and 
responsibility. 

 

5. TILT ANGLE 

The tilt angle is the measurement between the PV module and 
a  horizontal  ground  surface.  The  PV  module  generates  the 
maximum output power when it faces the sun directly. 
5 degrees or more is recommended for the tilt angle of the PV 
module for the maintenance (See 9. Maintenance). 
For  the  standalone  systems  with  a  battery  where  the  PV 
modules are attached to a permanent structure, the tilt angle of 
the  PV  modules  should  be  determined  to  optimize  the 
performance when the sunlight is the scarcest. In general, if the 
electric power generation is adequate when the sunlight is the 
scarcest, then the angle chosen should be adequate during the 
rest of the year. For grid-connected installations where the PV 
modules  are  attached  to  a  permanent  structure,  it  is 
recommended  to  tilt  the  PV  module  at  the  angle  equal  to  the 
latitude of the installation site so that the power generation from  
the PV module will be optimum throughout the year. 
 

6. WIRING 

To  ensure  proper  system  operation  and  to  maintain  your 
guaranty, observe the correct cable connection polarity (Figures 
1 & 2) when connecting the PV modules to a battery or to other 

PV modules. If not connected correctly, the bypass diodes could 
be destroyed. 
PV modules can be wired in series to increase voltage. Connect 
wires  from  the  positive  terminal  of  one  PV  module  to  the 
negative  terminal  of  the  next  PV  module.  Figure  1  shows  PV 
modules connected in series. 
Connect  PV  modules  in  parallel  to  increase  current.  Connect 
wires from the positive terminal of one PV module to the positive 
terminal on the next PV module. Figure 2 shows PV modules 
connected in parallel. 

7. GROUNDING 

The frame grounding must consider the local requirement and 
regulation at the installation site. When grounding is required, 
please refer to below example connection (Figure 3). Please be 
careful in arranging the system ground so that the removal of 
one PV module from the circuit will not interrupt the grounding 
of any other PV modules. 
The  PV  modules  should  be  grounded  to  the  same  electrical 
point as described below. 

You can use a hole with the appropriate symbol for equipotential 
bonding  on  the  side  frame  for  either  a  bolt,  nut  and  washer 
grounding the PV module to the frame, a ground lug fastened 
by bolt or screw, or appropriate screw (hardware not provided). 
An example of acceptable ground connection using a bolt, nut 
and  washer  retaining  a  ground  lug  is  shown  in  Figure  3.  In  a 
connection of this type, the hardware (such as a toothed locked 
washer  /  star  washer)  must  score  the  frame  surface  to  make 
electrical  contact  with  the  frame.  The  ground  wire  must  be 
considered within the local requirement of local and regulation 
at the site of installation. 
 

8. MOUNTING 

Please  make  sure  that  all  the  information  described  in  the 
INSTALLATION  MANUAL  is  still  valid  and  proper  for  your 
installation. The mounting method has been verified by SHARP 
and NOT CERTIFIED by a third party organization. 

 Bypass Diode 

(Built-in Junction Box) 

 Bypass Diode 

(Built-in Junction Box) 

Summary of Contents for NU-JC415

Page 1: ...ures e g snow stopper to avoid possible damage 13 Periodically remove any overhanging snow and or ice from the PV module framework as it may cause deformation of the PV module frame GENERAL INSTRUCTIONS 1 INTRODUCTION This INSTALLATION MANUAL contains essential information for the electrical and mechanical installation that you must know before installing SHARP PV modules This also contains safety...

Page 2: ...ers and circuit breakers immediately should a problem occur 17 In case the glass surface of a PV module is broken wear goggles and tape the glass to keep the broken pieces in place 18 A defective PV module may generate power even if it is removed from the system It may be dangerous to handle the PV module while exposed to sunlight Place a defective PV module in a carton so PV cells are completely ...

Page 3: ...aximum output power when it faces the sun directly 5 degrees or more is recommended for the tilt angle of the PV module for the maintenance See 9 Maintenance For the standalone systems with a battery where the PV modules are attached to a permanent structure the tilt angle of the PV modules should be determined to optimize the performance when the sunlight is the scarcest In general if the electri...

Page 4: ...of wiring and the state of the jacket of wires occasionally The PV modules is equipped with anti reflective coating glass do not touch the glass since finger prints or stains will easily mark If dirt build up becomes excessive clean the glass surface with water only INSTALLATION INSTRUCTIONS PHOTOVOLTAIC MODULES 1 INSTALLATION Mounting Using Clamps The PV modules can be mounted with clamps clips a...

Page 5: ...calculated under the condition of Voc at 40 C Under normal conditions a PV module is likely to experience conditions that produce more current and or voltage than reported at Standard Test Conditions Accordingly the values of Isc and Voc marked on this PV module should be multiplied by a factor of 1 25 when determining component voltage ratings conductor current ratings fuse sizes and size of cont...

Page 6: ...teel Material Stainless steel Diameter M8 8 2 15 4 mm Diameter M8 8 5 15 5 mm Thickness 2 mm reference value Thickness 1 6 mm reference value 3 Bolt 4 Nut Material Stainless steel Material Stainless steel Size M8 Size M8 Diameter M8 x 20 mm Fig B1 The components for BOLT NUT ...