[3] DIAGNOSIS PROCEDURE
1. AH-129 / AH-MP14
When indoor fan motor is out of order occurs, indoor fan motor and louver are all stopped and the operation LED(red) turns on or off
synchronously with the timimg of the timer LED.
When the thermistor for room temperature or pipe temperature is open or short state, the operation LED turns on or off synchrnoously with the
timing of the timer LED by pushing continously for more than 5 seconds "AUX." button during suspension of operati
Timing chart of Timer LED and Operation LED of DIAGNOSIS PROCEDURE.
When "OI" button the remote controller or "AUX." button in the unit is pushed, the unit is free from DIAGNOSIS
When the louver unit is not properly installed, all lamps on the indicator panel will blink operation are all stop and Remote signal is not accept.
PROCEDURE
13
Summary of Contents for AH-129
Page 7: ... 2 MICRO COMPUTER CONTROL SYSTEM 1 Electronic Control Diagram Indoor unit AH 129 AH MP14 7 ...
Page 8: ...2 PRINTED WIRING DIAGRAM 2 1 Indoor AH 129 8 ...
Page 9: ...2 2 Indoor AH MP14 9 ...
Page 14: ...CHAPTER 4 TROUBLESHOOTING 14 ...
Page 15: ...CHAPTER 4 TROUBLESHOOTING 15 ...
Page 16: ...16 ...