AH-X127E
AU-X127E
AY-X127E
AE-X127E
19
FUNCTIONS
k
j
i
h
g
f
e
d
c
b
a
z
+1.66
+1.00
+0.33
-0.33
-0.66
-1.00
-1.33
-1.66
-2.00
-2.33
Heating
SET VALUE
c
d
e
f
g
h
i
j
+1.33
+1.00
-0.33
-0.66
SET VALUE
+0.66
Cooling
+0.33
AH-X127E is not provided with the heating
function.
1. INDOOR UNIT
1-1 Temperature Adjustment
a. Normal control
Proportional control (P control)
When the temperature zone changes, this control
changes the frequency by one rank to move closer
to the set value.
Integral control (I control)
When the temperature zone has set time in the
same zone, this control changes the frequency by
one rank to move closer to the set value. (Excluding
the h zone.)
b. Initial control
The initial frequency is determined as shown in the
tables below based on the difference between the
temperature adjustment setting at the beginning of
operation and the room temperature.
After operation begins, normal control is performed
and therefore the correspondences in the tables
below will not hold.
c. Temperature adjustment
The temperature adjustment range is changed by
changing the operating mode with the operation
switch.
(1) Heating
If the room temperature is in the z zone when
operation begins, proportional/integral control is not
performed, and the machine runs at frequency code
c full power until the h zone is reached. When the h
zone is reached, the frequency changes to the
frequency code determined by fuzzy calculation,
and after that proportional/integral control is
performed.
(2) Cooling
If the room temperature is in the c zone when
operation begins,proportional/integral control is not
performed, and the machine runs at frequency
code 9 power until the h zone is reached. When the
h zone is reached, the frequency changes to the
frequency code
determined by fuzzy calculation,
and after
thatproportional/integral control is
performed.
(3) Dry
After operation begins, 2 minutes (running at the h
zone) of the room temperature is stored in memory,
and that becomes the set value.
(4) Circulation
The frequency code 0 is sent to the outdoor
machine, and only the fan of the indoor machine
runs, the compressor does not run.
e
f
f
h
i
+1.33
+1.00
-1.00
+0.33
Dry
MEMORY SET VALUE
Cooling
Room
temp.
zone
Frequency
Code
c
9
d
8
e
7
f
5
g
3
h
2
i
1
j
OFF
Heating
Room
temp.
zone
Frequency
Code
k
OFF
(Hot keep fan)
j
1
i
1
h
2
g
3
f
4
e
5
d
6
e
7
f
5
g
3
h
2
i
1
Dry
Room
temp.
zone
Frequency
Code
e
4
f
3
g
2
h
1
i
OFF
c
b
a
z
8
A
B
C