For the RS485 port, enter:
- Address (1-247 for
Modbus); (1-65520 for DNP)
- Protocol (Modbus RTU, Modbus ASCII, or DNP3)
- Baud Rate (1200, 2400, 4800, 9600, 19200, 38400, or 57600)
- Response Delay (0 - 750 in 50 ms increments)
Response Delay is the delay the meter should use before responding to queries.
- Parity (Odd, Even, or None)
Program Meter Time:
The meter is preset to Eastern time. To change the meter time:
1. From the Main screen’s Title bar, click Tools>Set Device Time.
2. You can either enter the time in the Time fields, or click Use
PC Time to set the time using your PC’s time.
3. Click Send.
NOTE:
The meter offers multiple Time Synchronization methods.
See Chapter 28, Section 28.1.3 in the software manual (click
Help>Contents from the Main screen to open the manual) for instructions on setting up Time Sync for
the meter.
Program Meter Name:
To enter an name/ID for the meter:
1. From the Device Profile screen, double-click General Settings>System Settings.