  5.1.5 BLIND DISTANCE

Press 

. The 

BLIND ZONE

 

is used to avoid undesi-
red measures near to the 
transmitter

Use 

 and 

 to modify the 

value. Press 

 to 

confirm. The minimum value 

is 50mm (PTU50), or 300mm 

(PTU51) or 500mm (PTU56).

  5.1.4 FILTER COEFFICIENT

Press 

. Increasing the

value slows down the sensor 
response speed.

Use 

 and 

 to modify the 

value. Input a value from 1 to 
99. Press 

 

to confirm.

In fig.24 value choice 

example.

Fast resp.

5÷10

Normal resp.

20

Slow resp.

40÷100

BLIND 

DISTANCE

PTU50-51-56

Refernt point 

BLIND

ZONE

Fig.24

Fig.25

PTU5x

 

- Quick Start

  5.1.8 DISPLAY

Press 

 to access the 

settings change. 

With the 

 button is pos-

sible to select the data to 
display

Press 

 to confirm.

Documentation subject to technical change with no prior warning

SGM-LEKTRA S.r.l. 

Via Papa Giovanni XXIII, 49 - 20090 Rodano (MI)  - ITALY-

tel: 

++39 0295328257

  fax: 

++39 0295328321

  

web: 

www.sgm-lektra.com

  e-mail: 

[email protected]

Pages from 9 to 20 (full manual) can be downloaded from our website 

www.sgm-lektra.com

 in the products section

5.2 ECHO MAP

Pressing the 

BK

, from RUN mode, to access directly to the echoes digital 

map display, which are in 

PTU50-51-56

 receiving (Fig.26).

This function is useful for:
  -  properly orient the transducer pointing.
  -  verify the echoes in acquisition correctness.
  -  identify any false echo signals that may cause measurement  errors.

OK

OK

B K

BK

D I S T:        7 2 1 m m

1

2

3

4

5 m

D I S T:        7 2 1 m m

1

2

3

4

5

m

echo signal normalization

Threshold  

Distance measured 

from PTU51-56 in 

real time

The rectangle placed at the echo line base, indicates the 

measurement range within which the echo signal in reception is 

considered always valid for the distance measurement. This 

interval value is variable depending on the measurement 

conditions: min. ± 2.5% of the measured distance

6

Fig.26

Fig.27

Summary of Contents for PTU5 Series

Page 1: ...Certificate In conformity to the company and check procedures I certify that the equipment PTU Production and check date Serial n is conform to the technical requirements on Technical Data and it is...

Page 2: ...PTU51 and PTU56 units are compact sensors and have a via connector quick connection The IP68 protection makes them suitable for external applications with direct exposure to the weather including are...

Page 3: ...for 12m max PTU56 range where the sensor can not measure PTU50 1 5m PTU51 6m PTU56 12m D mm Lmax mm D mm Lmax mm 100 80m 125 240 125 240 150 300 150 300 Fig 10 Fig 11 Tab 2 2 3 Mounting precautions 2...

Page 4: ...illing and emptying In the programming menu to the PRODUCT parameter must select the LIQUID PIPE option see page 7 or 11 2 3 5 Agitators presence The level measurement is possible thanks to the Auto T...

Page 5: ...tighten the connector ring nut position the cable so that it forms a downward curve at the M20 output Fig 18 in this way the condensation and or rain water will tend to drip from the curve bottom Fig...

Page 6: ...ification OK BK Exit configuration Back to previous menu Eco map from RUN mode Parameters values selection Parameters scroll Fig 21 PTU5x Configuration and Quick Start 5 QUICK START MODE From RUN mode...

Page 7: ...U50 1 5m max 300mm PTU51 6m max 500mm PTU56 8m max 5 1 Struttura men di configurazione rapida 4mA distance 20mA distance 100 0 Level measurement PTU50 51 56 referent point Fig 22 5 1 1 SET DISTANCE 4m...

Page 8: ...II 49 20090 Rodano MI ITALY tel 39 0295328257 fax 39 0295328321 web www sgm lektra com e mail info sgm lektra com Pagesfrom9to20 fullmanual canbedownloadedfromourwebsitewww sgm lektra comintheproducts...

Reviews: