SGM LEKTRA PTU5 Series Installation Manual Download Page 1

Technical Data

Housing material: 

PP  

Mechanical installation:     

1”GAS M; (PP flange

 DN100 opt.)

Protection degree:

 

 

IP68          

Electrical connection:

 

IP68 male connector

with 5/10/15/20m linking cable

Working temperature: 

-25° ÷ +75°C

Pressure: 

 da 0,5 a 1,5 bar (absolute

)

Power supply: 

 

24Vdc    

Power consumption: 

  1,5W 

Analog output:

 

4÷20mA max 750ohm

Digital communication: 

 MODBUS RTU  

Max measure range:

  PTU50 0.05÷1.5m; PTU51 0.3÷6m; 

PTU56 0,5÷12m 

[

In case of non perfectly  reflecting surfaces, the maximu 

distance value  will be reduced] 

Temperature compensation: 

digital in the working temperature

 

Accuracy:

 

±0,2% (of  the measured distance)

not better than ±3mm (PTU50 ±1mm)

Resolution: 

1mm

Calibration: 

 VLW601 prog. module with 4 buttons

or by MODBUS RTU

Warm-up: 

30 

minutes typical

LCD Display:

   matrix LCD 

display on VLW601 module (opt.) 

PTU50-51-56

Ultrasonic level transmitter

825B124C

Process Controll and Measurement

  Factory Test Certificate

In conformity to the company and check procedures I certify that the equipment:

PTU

................... 

 

Production and check date:     ................................

Serial n. 

  .......................................................

is conform to the technical requirements on Technical Data and it is made in conformity to the SGM-LEKTRA  procedure

Quality Control Manager  

          .................................

 Warranty

Products supplied by SGM LEKTRA are guaranteed for a period of 12 (twelve) months from delivery date according to 

the conditions specified in our sale conditions document.

SGM LEKTRA can choose to repair or replace the Product.

If the Product is repaired it will mantein the original term of guarantee, whereas if the Product is replaced it will have 12 

(twelve) months of guarantee.

The warranty will be null if the Client modifies, repair or uses  the Products for other purposes than the normal conditions 

foreseen by instructions or Contract.

In no circumstances shall SGM LEKTRA be liable for direct, indirect or consequiential or other loss or damage whether 

caused by negligence on the part of the company or its employees or otherwise howsoever arising out of defective goods

PTU51

PTU56

PTU50

Summary of Contents for PTU5 Series

Page 1: ...Certificate In conformity to the company and check procedures I certify that the equipment PTU Production and check date Serial n is conform to the technical requirements on Technical Data and it is...

Page 2: ...PTU51 and PTU56 units are compact sensors and have a via connector quick connection The IP68 protection makes them suitable for external applications with direct exposure to the weather including are...

Page 3: ...for 12m max PTU56 range where the sensor can not measure PTU50 1 5m PTU51 6m PTU56 12m D mm Lmax mm D mm Lmax mm 100 80m 125 240 125 240 150 300 150 300 Fig 10 Fig 11 Tab 2 2 3 Mounting precautions 2...

Page 4: ...illing and emptying In the programming menu to the PRODUCT parameter must select the LIQUID PIPE option see page 7 or 11 2 3 5 Agitators presence The level measurement is possible thanks to the Auto T...

Page 5: ...tighten the connector ring nut position the cable so that it forms a downward curve at the M20 output Fig 18 in this way the condensation and or rain water will tend to drip from the curve bottom Fig...

Page 6: ...ification OK BK Exit configuration Back to previous menu Eco map from RUN mode Parameters values selection Parameters scroll Fig 21 PTU5x Configuration and Quick Start 5 QUICK START MODE From RUN mode...

Page 7: ...U50 1 5m max 300mm PTU51 6m max 500mm PTU56 8m max 5 1 Struttura men di configurazione rapida 4mA distance 20mA distance 100 0 Level measurement PTU50 51 56 referent point Fig 22 5 1 1 SET DISTANCE 4m...

Page 8: ...II 49 20090 Rodano MI ITALY tel 39 0295328257 fax 39 0295328321 web www sgm lektra com e mail info sgm lektra com Pagesfrom9to20 fullmanual canbedownloadedfromourwebsitewww sgm lektra comintheproducts...

Reviews: