VACUUM LEAK DETECTOR
VLXE .. Ex M and VLXE .. Ex MMV
28/07/2020
- 16 -
4.6.4 “Tightness inquiry” function
Press and hold the „Mute“ button until the signal lamp is flashing rap-
idly, then release it. The display (103) will show a tightness value and
the same value will be indicated by the number of “Alarm” signal lamp
flashes.
This display disappears after 10 seconds and the current vacuum in
the system is displayed again.
For the "Tightness inquiry" function, the leak detector must have per-
formed at least 1 automatic refilling interval under normal operating
condition (i.e. without external filling, e.g. by an installation pump) to
achieve a valid statement.
This inquiry is recommended before performing a regular functional
check of a leak detector. In this way, it is possible to estimate imme-
diately whether it is necessary to look for leaks.
Number of flash signals
Assessment of tightness
0 Very
tight
1 to 3
Tight
4 to 6
Sufficiently tight
7 to 8
Maintenance recommended
9 to 10
Maintenance urgently recommended
The smaller the above value, the tighter the system. The significance
of this value also depends on temperature fluctuations and should
thus be considered a reference point.
Design and Function
(103)
Summary of Contents for VLXE Ex M Series
Page 49: ...28 07 2020 VACUUM LEAK DETECTOR VLXE Ex M and VLXE Ex MMV 49 12 7 Ex approval Appendix ...
Page 50: ...VACUUM LEAK DETECTOR VLXE Ex M and VLXE Ex MMV 28 07 2020 50 Appendix ...
Page 51: ...28 07 2020 VACUUM LEAK DETECTOR VLXE Ex M and VLXE Ex MMV 51 Appendix ...
Page 52: ...VACUUM LEAK DETECTOR VLXE Ex M and VLXE Ex MMV 28 07 2020 52 Appendix ...
Page 54: ...VACUUM LEAK DETECTOR VLXE Ex M and VLXE Ex MMV 28 07 2020 54 Appendix ...