OVERPRESSURE LEAK DETECTOR DLR-GS ..
10/09/2014
- 2 -
1. Subject
Overpressure leak detector without built-in pressure generator for double-walled pipes and
fittings, with inert gas or air used as the leak detection medium.
DLR-GS .. (the dots are replaced by the respective alarm pressure in bar)
2. Area of use
2.1. Requirements for interstitial spaces
Verification of the pressure resistance of the interstitial space (see Appendix B, column
"p
TEST
" for the minimum test pressure for the interstitial space)
Verification of suitability of the interstitial space (for Germany: building authority certificate of
suitability).
Leak-tightness of the interstitial space (see section 6.4.4)
The number of interstitial spaces to be monitored depends on the overall volume of the
interstitial space. According to EN 13160, this must not exceed 10m
3
. In order to make it
possible to verify the leak tightness of the interstitial space, we recommend that a value of
4 m
3
is not exceeded.
The length of pipe which is to be monitored (per pipe branch) should not exceed 2500 m or
as specified in the approval requirements of the pipeline.
2.2. Pipes
Double-walled pipes made of metal or plastic, assembled in the plant or on-site.
For Germany: more far-reaching requirements for double-walled pipes may result from
TRbF 50, the DIBt approval principles or EN 13160.
ONLY for applications where temperature fluctuations will not exceed
10°C (e.g. double-
walled pipes installed underground or through buildings; no hot fluids).
2.3. Fittings
Double-walled fittings made of metal or plastic, assembled in the plant or on-site.
For Germany: with Allgemeine bauaufsichtliche Zulassung (General Building Authority
Approval), where not included in the approval of the pipeline.
ONLY for applications where temperature fluctuations will not exceed
10°C (e.g. fittings
installed underground or in buildings; no hot fluids).
2.4. Materials carried in the pipes / leak detection medium
Water-pollutant
fluids
– With flashpoint >55°C with air or inert gas used as the leak detection medium
– With flashpoint <55°C with inert gas used as the leak detection medium as long as
the interstitial space has been classified by the operator as zone 2
– Which do not react with the leak detection medium