14
EN
WARNING
Definition of warning signs:
Indication that a risk of electrical origin exists.
Indication that a risk exists for the machine or its operation.
Directions to be used only by qualified professionals.
Disconnect electrical power before working on the unit!
2
DESCRIPTION
2.1 OPERATING PRINCIPLE
Sanicondens® Best Flat
contains a pump. The tank of the
Sanicondens® Best Flat
has a built-in a float which
controls the operation of the motor. When the condensate enters the tank, the pump starts up.
Sanicondens® Best Flat
has also a built-in secondary float that can trigger an alarm (audible and/or visual) and a
condensate neutralization system.
2.2 TECHNICAL DATA
Type
CD 10
Sound level
< 45 dBA
Max. vertical pumping
4.5 m
Average operating temperature
35°C
Maximum flow rate
380 L/h
Maximum allowable temperature
80°C
S3 15% (1min30 ON/8min30 OFF)
Min. pH
2.5
Level ON/OFF
56 mm / 46 mm
Weight of the unit
2 kg
Voltage
220-240 V
Tank volume
3.5 L
Frequency
50 Hz
Supply cable
1.5 m
Current consumption
0.52 A
Discharge hose
5 m, Øint: 10mm
Power rating
60 W
Alarm cable (2 cores)
1.5 m
Electrical class
I
Max. power for the connected
boiler
gas: 80 kW / oil: 50 kW
Protection index
IP20
Wall mounting
Yes
2.3 LIST OF PARTS SUPPLIED
see pg. 6.
2.4 DIMENSIONS
see pg. 11.
2.5 PERFORMANCE CURVES
see pg. 11.
2.6 VERTICAL PUMPING/HORIZONTAL PUMPING
see pg. 11.
1
AREA OF APPLICATION
Sanicondens® Best Flat
is a pump used to lift condensation water from an air conditioning system, a condensation
boiler, dehumidifiers or from refrigeration units. The unit has its own neutralisation system that can be used to
increase the pH of the acid water from the condensing boiler.
The pump starts automatically and has a high level of performance, safety and reliability as long as all the installation
and maintenance instructions mentioned in this manual are strictly followed.
All applications other than those described in this manual are prohibited.
3
START UP
3.1 INSTALLATION
Always install the pump: - horizontally, using a leveling tool,
- as close as possible to the appliance keeping in mind that the condensate has to
drain through gravity into the pump.
To ensure proper ventilation of the motor, the pump must be free of any obstruction.
The pump can be mounted against a wall using the wall bracket
C
provided:
- Fix the wall bracket
C
horizontally with the plastic anchors
A
and screws
B
supplied (accessory bag). See fig.
1
and
2
.
- Snap the
Sanicondens® Best Flat
onto the bracket: fig.
3A
and
3B
.
- Check that the
Sanicondens® Best Flat
is leveled: fig.
3C
.
3.2 HYDRAULIC CONNECTION
Connecting the inlet
The pump has two inlets that can be used as required:
- The upper inlet is open. If the upper inlet is used (fig.
5
), close the lower side inlet with the supplied gasket
F
, cover
G
and plug
E
(fig
4.2
).
- To use the lower side inlet (fig.
4.1
), place the plug
E
and Ø 32 mm gasket
F
on the inlet pipe and screw it onto the
inlet.
Drain the condensate water to any of these inlets. If necessary, use a rubber flexible adapter
D
.