Manual – MOVIDRIVE® MDX61B Synchronous Operation Board DRS11B
6
Parameter descriptions
Parameter
P516 X41 Encoder
monitoring
Setting range: NO / YES
•
NO: Wire breakage between the frequency inverter and a TTL encoder connected at
X41 is not recognized directly. In case of a defective connection, error F42 "Lag
error" will be issued in enabled state unless it has been deactivated.
•
YES: Wire breakage between the frequency inverter and a TTL encoder connected
at X41 is recognized directly. The error message F48 "Hardware DRS" will be issued
in case of an error. This error will also be generated in inhibited state.
P517 X41 Pulse
count monitoring
Setting range: NO / YES
The number of pulses of the encoder connected at X41 is checked using the resolution
set in P233 through evaluation of the C track. If increments are lost, the error message
F48 "Hardware DRS" is generated.
•
NO: Pulse counter monitoring is not active.
•
ON: Pulse counter monitoring is active.
P518 X42 Encoder
monitoring
Setting range: NO / YES
•
NO: Wire breakage between the frequency inverter and a TTL encoder connected at
X42 is not recognized directly. In case of a defective connection, error F42 "Lag
error" will be issued in enabled state unless it has been deactivated.
•
YES: Wire breakage between the frequency inverter and a TTL encoder connected
at X42 is recognized directly. The error message F48 "Hardware DRS" will be issued
in case of an error. This error will also be generated in inhibited state.
P519 X42 Pulse
count monitoring
Setting range: NO / YES
The number of pulses of the encoder connected at X42 is checked using the resolution
set in P234 through evaluation of the C track. If increments are lost, the error message
F48 "Hardware DRS" is generated.
•
NO: Pulse counter monitoring is not active.
•
ON: Pulse counter monitoring is active.
Encoder monitoring is not a safety function!
Encoder monitoring is not a safety function!