4
Startup
Activating local mode with DSC and SNI units
Addendum to the Operating Instructions – GBG10..A..
12
4.2
Activating local mode with DSC and SNI units
Local mode with the CBG10..A keypad is only possible if you activate local mode us-
ing DIP switch S2/3 of the drive unit.
To activate local mode, set DIP switch S2/3 of the drive unit to "ON" position as shown
in the following figure:
S2
ON
1
2 3 4
20741350155
•
When DIP switch
S2/3
is set to
"OFF"
, the drive unit uses the motion control in-
puts only for evaluating external sensors.
Local mode is not possible with this setting.
•
When DIP switch
S2/3
is set to
"ON"
, you can control the drive unit in automatic
mode (bus control) or local mode depending on the position of the "MODE" switch.
4.2.1
Requirements for local mode
The following requirements must be met for operating and switching the unit to local
mode:
Requirements on
the drive unit
Firmware for command PCB
Drive status
1)
MOVIGEAR
®
DSC/SNI
DRC..
DSC/SNI
From version .11
From version .10
Inhibited
1) Required drive status for switching to local mode
Requirements on
the controller
Application software on the controller
1)
ApplicationConfigurator
(CCU parameterizable)
From version 170.100
MultiMotion
(freely programmable)
From version 170.100
1) e.g. MOVIFIT® FDC
23569654/EN – 07/2017