4
Mechanical installation
Preliminary work after longer periods of storage
Operating Instructions – AC Motors
33
If the measured resistance is within the range of the limit characteristic curve (depend-
ing on the ambient temperature), the insulation resistance is sufficient. If the value is
below the limit characteristic curve, dry the motor.
100
10
1
0.1
0
20
40
60
80 °C
MΩ
9007199428064011
25851535/EN – 02/2019