background image

TRX UNIT BOOMERANG SF 6P150 

 

L

1

 

Front eject slot 

L

2

  Plastic front eject slot cup 

A

 

IR intensity adjustment trimmer  

B

 

Fire Led (RED) 

 * 

On  forewarning 

 * 

Blinking 

alarm 

C

 

Fire threshold adjustment trimmer 

D

 

Smoke threshold adjustment trimmer 

E

 

Smoke Led (RED) 

 * 

On  forewarning 

 * 

Blinking 

alarm 

F

 

IR intensity level Led (YELLOW) 

 

 

* On 

IR intensity level too low 

 

* Off 

Normal operating IR power 

 

* Blinking IR intensity level too high 

G

 

UTA Jack socket 

Power ON Led (GREEN) 

Vertical movement knob 

H

 

Horizontal  movement knob 

 
REFLECTION DEVICE MODEL 6P150 

 

In  this model the reflection device is  pro-
vided by a micromechanical reflector device 
affixed to the opposite wall.

 

 

BOOMERANG SF 6P150 ASSEMBLY AND SETTING UP PROCEDURE 

 

1  Fix the TRX mounting bracket and plug in the TRX device. Aim it roughly in the direction of the selected  microme-

chanical reflector unit opposite. 

Fix the reflector micromechanical unit on the opposite side and aim it roughly  in the direction of the TRX

3  Connect the wires as in the wiring diagram in the INT8BA and the TRX. Switch on the system and rotate trimmer “A” 

18 turns in a clockwise direction. The Yellow Led can be in one of three possible states: either flashing, or ON, or 

OFF. The Led ON means the IR return light beam is too low; if the Led is flashing the IR reflected beam is too high ; if 

it is OFF the IR light beam reflected is roughly acceptable. This condition could be a fault in this phase. 

Align the TRX device using the adjustment knobs “V” and “H”.  The required state at the end of  this phase is  with the 

yellow led flashing.

 

5  Rotate the TRX using adjustment knob “H” in the horizontal plane to the right until the yellow led “F” stops flashing 

and goes out. Counting the number of turns of the knob turn back to the left side turning and counting until the yellow 

led stops flashing and goes out. During operation the Smoke red flashing led can light up in alarm mode. This is nor-

mal. Reset by removing the connector to the TRX for min. 3 seconds.  

Divide the number of turns two and turn by that amount towards the middle. You have now found the centre of the IR 

beam in the horizontal plane. Repeat the above procedure using knob “V” for finding the centre of the IR beam in ver-

tical plane. In this situation the yellow Led must be flashing and the trouble interface relay will also operate ON/OFF 

intermittently. This state is essential in this phase. 

 

7  Repeat the procedure in 6 above for the micromechanical reflection device at the opposite position finding the centre 

of the two axes looking from the opposite side at TRX’s yellow led (E) i.e. ON-OFF-Flashing. 

8  Now, for the micromechanical reflection device, cover the reflector with a piece of card or paper. Looking toward the 

TRX  unit, the yellow Led will flash without covering. When you cover the micromechanical reflection device the TRX 

switches off the flashing yellow led and lights the ON light continuously. After removing the obstruction the yellow led 

will flash again. If it does not, check whether there is any shiny reflecting surface along the IR path between the TRX 

and reflector device.  

When both devices are aligned and the yellow TRX device led is flashing, rotate the trimmer “A” anticlockwise until it 

stops flashing and goes out, When the led switches off it means the IR strength is accepted by the TRX. Half turn the 

trimmer “A” clockwise with the led OFF before replacing the front cover and the slot cup. 

 

L1 

Clockwise 

Anticlockwise 

 

L2 

Summary of Contents for Boomerang SF 6P150

Page 1: ... reflector response If a part of IR light is reflected back by surfaces other than this reflector device different TRX positions should be selected Do not place this model of detector in warehouses where the goods stored are closer than 1 20m to the ceiling or roof Keep the whole path whole detector path distance between the TRX and reflector device as clear as possible Avoid detector placement in...

Page 2: ...ght until the yellow led F stops flashing and goes out Counting the number of turns of the knob turn back to the left side turning and counting until the yellow led stops flashing and goes out During operation the Smoke red flashing led can light up in alarm mode This is nor mal Reset by removing the connector to the TRX for min 3 seconds 6 Divide the number of turns two and turn by that amount to...

Page 3: ...peak to our authorised technical services f Switch OFF and disconnect the UTA Jack plug store the instrument in a cool dry place with its batteries removed CALIBRATION PROVIDED BY ADM DEVICE AND MULTIMETER If an ADM is being used a Insert the ADM jack plug in the TRX socket Switch on ADM and select detector mode Insert the ADM s plugs in to multimetr respecting the polarity Set the multimeter scal...

Page 4: ...N 2 Delay 30 POSITION 3 Delay 60 POSITION 4 Delay 90 1 2 3 4 5 6 7 8 24V GND NO C NC NO C NC TERMINALS NOT USED IN BOOME RANG MODELS 104 mm 130 mm 104 mm inserted not inserted RRX ABSORBTION MAX 24 VOLT interface included mA MAX JB IN JB OUT NORMAL WORKING 80 94 TROUBLE 108 94 ALARM 100 114 130 mm www setronicverona com LINE LINE ...