LINEAR OPTICAL REFLECTING BEAM SMOKE DETECTOR
SF
6P150
distance: min 71m to max 150m
VARIABLE POSITIONING RELATIVE TO THE PLANE THE BRACKET IS FASTENED ON AND
MICROMECHANICAL REFLECTOR DEVICE
ATTENTION
MODEL REQUIRES INTERFACE INT8BA
Before installing the detectors, check the wall or surfaces on which the TRX brackets and micromechanical reflector
device are mounted. They must not be in any way subjected to movement or vibrations during the operation of the
units.
Before installing the units check whether there are any shiny or reflective surfaces crosswise between the beams
along the IR beam path between the TRX and the micromechanical reflector device. If there are, check whether they
interfere with the micromechanical reflector response. If a part of IR light is reflected back by surfaces other than this
reflector device, different TRX positions should be selected.
Do not place this model of detector in warehouses where the goods stored are closer than 1,20m to the ceiling or
roof.Keep the whole path whole detector path distance between the TRX and reflector device as clear as possible.
Avoid detector placement in front of or near to strong electric lights or bright sunlight.
If there are particularly problematic situations, one or more reflector device may be required and a diaphragm could
also be required as an additional accessory to be used according to the instructions provided.