3.1 Voltage and current output units

The Model AXD (voltage output) transducer is a 3-wire voltage device. It is operable in a 5000

Ω

 load 

or greater. The wires for the individual conductors is as follows:

Current output units

The Model AXD (current output) transducer is a true 2-wire, 4-20 mA current output device and delivers 

rated current into any external load of 0-800 ohms. The 4-20 mA units are designed to have current 

flow in one direction only - 

Please observe polarity

.  We suggest that the electrical cable shield be 

connected to the system’s loop circuit ground to improve electrical noise rejection.  The electrical 

connection is as follows:

CAUTION

:

 

Unit is reverse excitation protected. 

However, do not apply power to output lead as 

this could cause permanent damage.

The AXD has a 2-wire cable, where red is 

positive and black is negative.

Model AXD

 Setra transducer 

(4-20 mA)

Power

supply

Load

(monitor)

+

+

+

_

_

_

CAUTION: Reverse excitation will not cause damage 

to the unit unless voltage applied is above 50 VDC. 

However, the unit will not function if reverse wired.

Red + Excitation

Black - Excitation

+

Monitor or 

Control

Device

_

Green

+ Out

White

- Out

Shield

-Out

+Out

Model AXD

 Setra transducer 

(Voltage Output)

Voltage

Current output

3.2 Output wiring schematics

Model AXD:

 In case of electrical noise pickup we suggest connecting a 22 μF non-polar electrolytic 

capacitor rated 50V between (+Exc and -Exc) terminals of power supply to improve noise rejection. 

3.3 Electrical termination wiring instructions

Cable version ("XX")

Voltage

Current

Red

+Exc

+Exc/supply

Green

+Out

-Exc/return

Black

-Exc/common

N/C

White

N/C  /no connect

N/C

Shield

Earth ground/system ground

Earth ground/system ground

 

9.1 .36

 

 

21.8 .86

 

 

71.9 2.83

 

 

22.1 .87

 

 

27.9 1.10

 

25.4 1.00

SOAXD1XXXPGJ7XXP1XNN

REV.

 

 

DATE

REVISION RECORD

FILE:

DWG SIZE

> 6" = ±1/16

DO NOT SCALE DRAWING

< 6" = ±1/32

THIRD ANGLE PROJECTION

ANGULAR

A

± 0° 30"

FRACTIONAL

TOLERANCES

EXCEPT AS NOTED

DECIMAL

XX = ±.01

MATERIAL

DRAWING NUMBER

OUTLINE, AXD, 7/16 SAE FITTING W/3 PIN PACKARD

TITLE

SCALE

ENGR

REV.

DATE

1

APPROVALS

DESCRIPTION

DATE

Boxborough, MA, USA

MATERIAL

1:1

INITIALS

SAINT HILAIRE

1-24-19

SOAXD1XXXPGJ7XXP1XNN_1.DRW

 

 

DRAWN BY

XXX = ±.005

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 of 1

SHEET

©  SETRA SYSTEMS, INC.   THIS DRAWING CONTAINS THE PROPRIETARY INFORMATION OF SETRA SYSTEMS, INC., ALL RIGHTS RESERVED. ALL UNAUTHORIZED REPRODUCTION, USE AND TRANSMISSION OF THIS DRAWING AND  INFORMATION IT CONTAINS ARE STRICTLY PROHIBITED. THIS DRAWING IS SUBJECT TO RETURN TO SETRA SYSTEMS, INC., UPON ITS REQUEST.

3-pin packard connector ("P1")

Voltage

Current

A

–Exc/common

–Exc/return

B

+Exc

+Exc/supply

C

+Out

N/C

Type: P2S series 150

A

C

B

Vent ring

(Hydrophobic filter)

Summary of Contents for AXD

Page 1: ...ly standard pipe fittings and procedures should be used However for pressure ranges in excess of 500 psig we suggest the use of a sealant such as Locite Hydraulic Sealant Excessive torquing of metal fittings may cause a slight zero shift The use of plastic fittings typically results in no noticeable zero shift Torquing does not appreciably affect linearity or sensitivity 2 4 Venting Because the re...

Page 2: ...ative Model AXD Setra transducer 4 20 mA Power supply Load monitor _ _ _ CAUTION Reverse excitation will not cause damage to the unit unless voltage applied is above 50 VDC However the unit will not function if reverse wired Red Excitation Black Excitation Monitor or Control Device _ Green Out White Out Shield Out Out Model AXD Setra transducer Voltage Output Voltage Current output 3 2 Output wiri...

Page 3: ...sten the wires to terminals 3 Screw on the Model AXD top cover Hand tighten only 2Lb Ft 3N m max torque 4 Fit conduit into conduit fitting and tighten conduit liquid tight strain relief 3 4 EMC Certification This product complies with EN61326 electrical equipment for measurement control and laboratory use EMC requirements for minimum requirements and industrial locations Special caution should be ...

Page 4: ...ill repair or replace products found to be defective in materials or workmanship within the warranty period provided that a the product has not been subjected to abuse neglect accident incorrect wiring not our own improper installation or servicing or use in violation of instructions furnished by SETRA b the product has not been repaired or altered by anyone except SETRA or its authorized service ...

Reviews: