19
Operation
: Control panel
48
rH60
OK
OK
>
40
<
99
OK
COF
o
>
05
<
34
OK
OK
EFOF
>
40
<
99
OK
OK
SIOF
>
1
<
99
OK
OK
d001
>
1
<
255
OK
OK
Update to latest software version, if the menu looks different.
Code Function
Default
value
Value
range
Description
rH
Relative
humidity (%)
60
40-99 The unit will start dehumidifying, when the sen-
sor measures a relative humidity higher than the
set value. (Note the +/- 2% hysteresis)
°
C
°
Celcius
(accessory only)
OF
(OFF)
5-34 The el/water heating coil (accessory) will start
to heat, when the temperature is lower than the
set value. (Note the +/- 2
°
C hysteresis)
EF
Extractor fan
(accessory only)
OF
(OFF)
40-99 The extractor fan (accessory) will start, when the
humidity is higher than the set value, complete-
ly independent of the dehumidifier. The value is
measured in % relative humidity.
(Note the +/- 2% hysteresis)
SI
Service Interval
(weeks)
OF
(OFF)
1-99 When the Service Interval function is enabled,
the unit will display
SEr
, when it is time for
service.
d001 Modbus Slave ID
001
1-255 Connection via modbus is possible. The default
modbus slave ID of the unit is 1 and can be
changed to a value between 1-255.
Press and hold OK button for 3 sec to enter menu mode
Toggle Menu Page / change value
Note: If no button is pressed for 10 seconds it will return to Standard view.
Menu overview
Default view
Example
Menu description
OK
Menu buttons
en