Control
28
Menus
Sub-Menu RESET
Reset to factory setting value.
Sub-Menu MAN TEST
How to enter the Sub-Menu MAN TEST:
You need to choose the " MAN TEST" on the main menu ( INFORMATION) And press the right button for 3
second .
Man test for installation
On sub-menu OPERATION---MAN TEST
ADD1 / 2 / 3 ON or OFF
ADD1 / 2 / 3 ( electrical heater 1 / 2 /3 )
3 WAY
ON or OFF
3-WAY VALVE
4 WAY
ON or OFF
4-WAY VALVE
WARM PUMP
ON or OFF
WATER PUMP
This menu is for installation engineer, user operation is prohibitive. The testing function will dissolve as
soon as the menu is off the interface.
P.S : the compressor only runs 5 minutes for testing, at that time its frequency is 45Hz.
ADD 1
3 WAY
4 WAY
WARM PUMP
MAN TEST
OFF
OFF
OFF
OFF
OFF
ADD 2
OFF
ADD 3
OFF
CMP
OFF
CMP
OFF
B
CMP
ON or OFF
COMPRESSOR
CMP B
ON or OFF
COMPRESSOR B ( invalid )
BRINE PUMP
BRINE PUMP
ON or OFF
BRINE PUMP
Sub-Menu
ALARM RECORD
To record 8 alarm histories recently; the newest alarm message will be seen in the first line. Press the right
button to check alarm history.
ADD2
ADD3
(6kW) since installation. Operating time will
Total operating hours of auxiliary heater
will not be reset to zero.
(9kW) since installation. Operating time will
Total operating hours of auxiliary heater
will not be reset to zero.
can not
can not
Menu Text
Description
Adjustable by
HEATPUMP
Total operating hours of heat pump since installation.
Operating time will not be reset to zero.
ADD
Total operating hours of auxiliary heater 1
(3kW) since installation. Operating time will
not be reset to zero.
can not
can not
*