Control
26
Menus
Sub-Menu SETTING
EMERGENCY1 (ON or OFF)
EMERGENCY2(ON or OFF)
Emergency mode 1
˄
emergency 1
˅
:
˄
ON or OFF
˅ˈ
factory setting is OFF(after select emergency
mode, the unit will continuously execute the same objective (room heating only, water tank heating only,
or auto)
When select ON, compressor will be switch off, only electrical heater, water pump or other temperature
protection are available. When in water tank heating, the electrical heater will instead of compressor;
when in room heating mode, the electrical heater will runs depends on Integral; when in room heating
mode 1, the electrical heater will runs depends on Integral; when in room heating mode 2, the electrical
heater automatically starts, unless operator off the electrical heater.
Emergency mode 2
˄
emergency 2
˅
:
˄
ON or OFF
˅ˈ
factory setting is OFF: (after select emergency
mode, the unit will continuously execute the same objective (room heating only, water tank heating only,
or auto)
When select this mode, compressor will stop determined by outdoor ambient temperature, the
temperature setting is from 0 to -50 degree adjustable, factory setting is -25 degree, only electrical
heater, water pump or other temperature protection are available. When in water tank heating, the
electrical heater will instead of compressor; when in room heating mode, the electrical heater will runs
depends on Integral; when in room heating mode 1, the electrical heater will runs depends on Integral;
when in room heating mode 2, the electrical heater automatically starts, unless operator off the
electrical heater.
If the water tank’s temperature always less than 60
ć
(default) and last 360 hours(period), the heat
pump will start the sterilize function ( the electrical heater start as soon as water get to 50
ć
), until
water temperature get to 60
ć
(default) and last 10 minutes( default); or if 3 hours later the water
temperature still can not reach 60
ć
, the sterilize function will exit.
Sterilize water temperature:
˄
60
ć
--90
ć
adjustable
˅
default is 60
ć
Sterilize duration :
˄
10—90minutes
˅
default is10 minutes
Sterilize period :
˄
7----99days
˅
default is 15 days
STERTLIZE
PERIOD
DURATION
15 D
10 M
WATER TEMP 60
STERILIZE:
EMERGENCY 1
EMERGENCY 2
SETTING
OFF
OFF
ADD DELAY
30M
ADD DIF TEMP
4
ADD START
40
STERILAZE
HDO
WATER PUMP
ON
EMERGENCY 2
OFF
EMERGENCY 2
-25
CMP STOP
ADD ENFORCE
OFF