42
Sentry Equipment Corp
Register
Sample Sentry II Register
R/W
Format
30017 / 40017
Remote Stop/Permissive Run
Read / Write INT 16
30018 / 40018
Shutdown Flow Rate
Read / Write INT 16
30019 / 40019
Remote Blowdown/Sample Control
Read / Write INT 16
30020 / 40020
Empty
Read / Write INT 16
30021 / 40021
Shutdown Pressure
Read / Write INT 16
Additional Notes:
State (30001)
0 = Manual
1 = Closing Valve
2 = Start
3 = Blowdown
4 = Sample
5 = Stop
6 = Entering Manual
7 = Temperature Alarm
8 = Motor Alarm
9 = Remote Blowdown
10 = Remote Sample 11-14 = Auto Clean
Remote Start (40016)
Momentarily place a 1 in this register to remotely place the system in Auto. To place a
momentary 1 in this register, you need to write a 1 to this register for at least 1 second,
followed by writing this register back to zero.
Remote Stop/Permissive Run (40017)
Momentarily place a 1 in this register to remotely place the system in Manual. Maintaining
a 1 in this register functions as a remote lockout. To place a momentary 1 in this register,
you need to write a 1 to this register for at least 1 second, followed by writing this register
back to zero.
Remote Blowdown/Sample Control (40019)
0 = Local control of system
1 = Remote blowdown
2 = Remote Sample
Use this register to control the mode of the Sample Sentry II. A 0 in this register gives local
control to the system. Blowdown and Sample modes are initiated based on controller
setup parameters. Placing a 1 in this register places the system in Remote Blowdown. SV-2
remains closed preventing flow to online analyzers. The system overrides the blowdown
timer, remaining in the blowdown condition until this register changes or the system is
shutdown. Placing a 2 in this register places the system in Remote Sample.
Summary of Contents for Sample Sentry II High Pressure
Page 7: ...Sentry Sample Sentry II 7 Figure 1 Typical P ID of a Sample Sentry II System...
Page 8: ...8 Sentry Equipment Corp Figure 2 P ID of a Sample Sentry II system with Secondary Cooling...
Page 11: ...Sentry Sample Sentry II 11 Figure 3 Controller Front Panel...
Page 24: ...24 Sentry Equipment Corp Figure 25 General Arrangement High Pressure Model...
Page 26: ...26 Sentry Equipment Corp Figure 26 Electrical Wiring Diagram...
Page 43: ...Sentry Sample Sentry II 43 This page is intentionally left blank...
Page 44: ...44 Sentry Equipment Corp This page is intentionally left blank...