Ordering/Electrical Specifications
RESET
A
SAFE
AUX.
B
C
D
Emergency Stop Relay
INT-04
120 VAC
230 VAC
60 VDC
120 VAC
30 VDC
LOADS
E
F
G
INT04WIR
OUTPUTS
FUSE
–
+
L1
L2
1
2
X1 X2
Y1
Y2
N.O.
PART NUMBER
POWER INPUT
INPUT FUSE REQUIRED
INT-04-024
24VDC +/-15%, 100mA
Fast acting 1/4mA (250V, 5 x 20mm, F/T)
INT-04-120
10% -20%, 5VA, 50/60Hz
Fast acting 80mA (250V, 5 x 20mm, F/T)
European Directives
Machinery Directive (98/37/EEC)
Low Voltage Directive (73/23/EEC), LVD
Specific European Standards
EN60204-1 Safety of electrical equipment of industrial
machines: 1993
EN954-1 Risk Assessment Category 4
depending on wiring method, See diagrams: 1997
EN50081-2 Electromagnetic Emissions: 1995
EN50082-2 Electromagnetic Immunity: 1995
IEC 664-1 Insulation requirements: 1992
IEC 68, part 2-1, 2-2, 2-3, 2-6, 2-14, 2-27, 2-30.
EN1760-1:1998
Typical Wiring Diagram
General Specifications
Listings
TUV, UL E122942
Weight
INT-04-24
9oz
INT-04-120
15oz
Field wiring size
12 gauge max.
Environmental rating
Pollution Degree II
Controller rating
IP20
Temperature range
32
°
F to 149
°
F (-0
°
C to 65
°
C)
Relative humidity
30 to 95% non-condensing
Power Supply (+,- or L1, L2)
INT-04-024
24VDC +/-15%
Required fuse
1/4A (250V, 5x20mm, F/T)
INT-04-120
10%, -20%, 5VA, 50/60Hz
Required Fuse
80mA (250V, 5x20mm, F/T)
Control Inputs (X1, X2 & Y1, Y2 terminals)
Open-circuit voltage
24VDC
Closed-circuit current
24mA
Max. contact resistance
30 Ohms
Simultaneity
500ms typical
Safe Outputs (A, B & C, D terminals)
Voltage
230VAC/60VDC
Current
4A (resistive) each output
Response time
ON: <100msOFF: <100ms
Required Fuse
4A (250V, 5x20mm, F/T)
Life Expectancy
100,000 cycles
Signaling Outputs (E, F, and G terminals)
Voltage:
120VAC/30VDC
Current:
1A (resistive)
Declaration of Conformity
available upon request.
File E 122942
Auxillary Contacts
POWER
RESET (1, 2)
E-STOPS
E, F
F, G
Off
Open or Closed
Open or Closed
Closed
Open
On
Open
Open or Closed
Closed
Open
On
Open or Closed
Open
Closed
Open
On
Closed
Closed
Open
Closed
Reset “Open” is prior to initiating a cycle.
Reset “Closed” can be momentary to maintained.