background image

2

Figure 3 - Wiring Diagram

6. Attach the detector to the mounting base as follows:

-

 Line up the raised tab on the side of the detector with

  the arrow on the mounting base.  See Figure 4.

-

 Insert the smoke detector into the base and turn

  clockwise approximately 15 degrees.  It should snap

  firmly into place.

7. Apply power.
8. Test the detector.  See 

Smoke Testing the

 Detector.

Important

: The control panel alarm and all auxiliary

functions should be verified for a complete test of the

system.

Gasket

Mounting base

Detector

Figure 2 - Mounting the Detector

Smoke Testing the Detector

Smoke detectors should be tested in place annually using

smoke or canned aerosol simulated smoke.  Follow the

instructions on the canned smoke or use the following

steps to test the detector with smoke:
1. Hold a smoldering punk or cotton wick close to the

smoke entry openings.

2. Gently direct the smoke into the detector for 20 seconds

or until an alarm is indicated.

BE SURE TO PROPERLY EXTINGUISH THE SMOKE

SOURCE AFTER TESTING! 

 

The detector LED should

stay on and an alarm should be indicated at the control

panel.  Use the system reset switch to reset the detector.

Understanding the LED

The LED on the detector indicates the status of the detector

as follows:

Flashing every 9 seconds

 = Normal operation.

On

 = Detects smoke, sending an alarm.

Off or flashing once every 1.5 seconds

 = Trouble or

maintenance is required. Test the detector.  See 

Testing the

Detector Sensitivity.

Figure 4- Attaching Detector to Base

+

_

2-wire 
initiating
circuit

UL Listed control panel

First 
detector

Last 
detector

EOL
device

+

+

_

_

Reviews: