5.

All works must be carried out with equipment fully isolated from the power 
supply.

Make sure the connections are correct before you power the unit.

7. 

Close the cover.

8. 

Turn the knob at ‘0’.

9. 

Tighten the cable glands. 

10. 

Switch on the mains supply. 

11. 

 Make sure the transformer controller can operates normally (consider an isolating 

switch).

12. 

Turn the knob into the relevant position to adjust the output voltage. 

Optional settings

The standard configuration of the output voltages is as indicated in 

Table 1

 below. 

Table 1 Voltage 

Knob position

0

1

2

3

4

5

Regulated output [VAC]

80

110

140

170

230

Unregulated output [VAC]

0

230

230

230

230

230

VERIFICATION OF INSTALLATION

ATTENTION

Use only tools and equipment with non-conducting handles when working on 
electrical devices.

After connecting the unit to the mains supply, the green LED on its cover should 
light up indicating that the controller is supplied. 

 Safe operation depends on proper installation. Before start up, ensure the following:

 

The mains supply is connected correctly.

 

Protection is provided against electrical shock.

 

The cables are the appropriate size and fuse-protected.

 

There is sufficient air flow around the unit.

ATTENTION

The unit is supplied with electrical energy at voltages high enough to inflict personal 
injury or threat to health. Take the relevant safety measures. 

ATTENTION

Disconnect and confirm that there is no live current flowing to the unit before servicing.

ATTENTION

Avoid exposing the controller to direct sunlight!

 

ATTENTION

ATTENTION

STANDARD 3-PHASE 230 VAC 
TRANSFORMER CONTROLLER

STR-3

Summary of Contents for STR-3

Page 1: ...Mounting and operating instructions STANDARD 3 PHASE 230 VAC TRANSFORMER CONTROLLER STR 3 ...

Page 2: ...UTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION 7 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 STANDARD 3 PHASE 230 VAC TRANSFORMER CONTROLLER STR 3 ...

Page 3: ...s as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting servicing...

Page 4: ... 10 0 STR 3130L10 13 0 INTENDED AREA OF USE Speed control of voltage controllable 230 VAC three phase motors For indoor use only TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current depends on the version see article codes Unregulated output 230 VAC Wide power range 5 step rotary switch for manual control plus off position LED status indication Enclosure sheet steel RAL 7035 polyes...

Page 5: ...Mind the correct mounting position and unit mounting dimensions see Fig 1 Mounting dimensions and Fig 2 Mounting position 3 Pay attention to following instructions in order to minimize the operating temperature 3 1 Respect the distances both between the wall ceiling and the device and between two devices as shown in Fig 2 In order to ensure sufficient ventilation of the controller clearance on eve...

Page 6: ...tion Wiring and connections above 6 1 Connect the power supply lines terminals R S T and PE 6 2 Connect the motor s terminals U V W and PE 6 3 If applicable connect the unregulated output L1 and N It can be used to supply a 230 VAC valve lamp etc when the knob is not at 0 position see Table 1 below ATTENTION A safety isolator disconnect switch should be installed on the mains electricity side of a...

Page 7: ...FICATION OF INSTALLATION ATTENTION Use only tools and equipment with non conducting handles when working on electrical devices After connecting the unit to the mains supply the green LED on its cover should light up indicating that the controller is supplied Safe operation depends on proper installation Before start up ensure the following The mains supply is connected correctly Protection is prov...

Page 8: ...lterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be...

Reviews: