background image

www.sentera.eu

MIW-SDX-DM-EN-000 - 17 / 06 / 2021

5 - 8

back to the table of contents

SDX-DM

ELECTRONIC FAN SPEED 
CONTROLLER

 

 EN 61000-3-2:2014 Electromagnetic compatibility (EMC) – Part 3-2: Limits - 
Limits for harmonic current emissions (equipment input current ≤ 16 A per phase)

 

WEEE Directive 2012/19/EU

 

RoHs Directive 2011/65/EU

OPERATIONAL DIAGRAMS

Low to high speed with soft start

Low to high speed with kick start

Uout [%]

Min.

Max.

Off

 

Switch

On 

Potentiometer position

Umax

Umin

Uout [%]

Min.

Max.

Off

 

Switch

On 

Potentiometer position

Umax

Umin

Kickstart 

2—20 s

High to low speed with soft start

High to low speed with kick start

Uout [%]

Min.

Max.

Off

 

Switch

On 

Potentiometer position

Umax

Umin

Uout [%]

Min.

Max.

Off

 

Switch

On 

Potentiometer position

Umax

Umin

Kickstart 

2—20 s

NOTE

By default, the desired fan speed or output value is set via the built-in potentiometer. 
It is possible to overrule the built-in potentiometer via Modbus RTU communication. 
Output overwrite can be enabled via Modbus Holding register 12. When output 
overwrite is enabled, the desired output value can be written in Modbus Holding 
register 13. In that case it is advisable also to activate Modbus safety timeout 
by writing a value different from 0 in Holding register 8. After the time out period 
elapses, the output is forced to the minimum output value. If timeout is set to zero, 
this function is disabled.

ATTENTION

Overheating protection is activated when an excessive load is connected to the 
output or in case the ambient temperature exceeds the maximum allowed operating 
temperature. When overheating protection is activated, the output is disabled and 
overheat condition is indicated in Modbus input register 10. When the overheating 
condition is removed, the device automatically resumes operation.

WIRING AND CONNECTIONS

A

Modbus RTU communication, signals A and /B

/B
L

Power supply, line (230 VAC ±10 % / 50—60 Hz)

N

Power supply, neutral

U2

Regulated output to motor, neutral

U1

Regulated output to motor, line

Connections

Spring contact terminal block, cable cross section: 1,5 mm

2

; pitch 5 mm

Umax from 

75—100 % Us

Umin from 

20—70 % Us

Umax from 

75—100 % Us

Umax from 

75—100 % Us

Umax from 

75—100 % Us

Umin from 

20—70 % Us

Umin from 

20—70 % Us

Umin from 

20—70 % Us

Summary of Contents for SDX-DM Series

Page 1: ...SDX DM ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions ...

Page 2: ...ROLLER Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 ...

Page 3: ...product performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always dis...

Page 4: ...ed output to motor Umin Us Minimum and maximum output voltage are adjustable via Modbus RTU communication Vmin 20 70 of Us and Vmax 75 100 of Us Overheating protection Operating mode selectable via Modbus RTU from low to high speed or from high to low speed Enclosure External ASA white colour 28049P IP54 protection according to EN 60529 Internal polyamide natural colour IP44 protection according t...

Page 5: ...en output overwrite is enabled the desired output value can be written in Modbus Holding register 13 In that case it is advisable also to activate Modbus safety timeout by writing a value different from 0 in Holding register 8 After the time out period elapses the output is forced to the minimum output value If timeout is set to zero this function is disabled ATTENTION Overheating protection is ac...

Page 6: ...ove the cover of the external enclosure 4 Do the wiring according to the wiring diagram see Fig 1 Wiring and connections 5 Mount the internal enclosure into the wall according to the mounting dimensions shown in Fig 2 Mounting dimensions inset mounting Fig 1 Wiring and connections Power Supply 230 VAC 50 60 Hz Regulated output to motor Modbus RTU communication Fig 2 Mounting dimensions Inset mount...

Page 7: ...the surface by means of the screws and dowels adhering to the mounting dimensions shown in Fig 3 Mounting dimensions surface mounting Fig 3 Mounting dimensions surface mounting 64 64 82 89 63 5 82 Correct Incorrect 5 Insert the cables through the grommets 6 Do the wiring according to the wiring diagram see Fig 1 Wiring and connections 7 Insert the internal enclosure into the external one and fix i...

Page 8: ...he controller is not overheated the Modbus communication is available all connections are correct the machine to be regulated is functioning TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relie...

Reviews: