SDX-DM

ELECTRONIC FAN SPEED 
CONTROLLER

PRODUCT DESCRIPTION

The SDX-DM series are electronic fan speed controllers, which allow you to manually 
adjust the rotational speed of single phase AC motors by varying the motor voltage 
through phase angle control. The output can be regulated from minimum to maximum  
or from maximum to minimum. The operating mode can be selected via Modbus 
RTU. The controller is suitable for both inset (IP44) and surface mounting (IP54). All 
parameters and settings can be adjusted via Modbus RTU communication.

ARTICLE CODES

Output regulation (from low to high or from high to low)

Code

Rated current range [A] 

SDX-1-15-DM

0,1—1,5

SDX-1-25-DM

0,2—2,5

INTENDED AREA OF USE

 

Manual control of the motor / fan speed in HVAC applications

 

For indoor use only

TECHNICAL DATA

 

Inset or surface mounting

 

Supply voltage (Us): 230 VAC / 50—60 Hz

 

Spring contact terminal block

 

Motor acceleration: kick start (from 2 to 20 seconds) or soft start

 

Regulated output to motor: Umin—Us

 

 

Minimum and maximum output voltage are adjustable via Modbus RTU 
communication. Vmin: 20—70 % of Us and Vmax: 75—100 % of Us

 

Overheating protection

 

 Operating mode selectable via Modbus RTU: from low to high speed or from high 
to low speed

 

Enclosure: 

 

External: ASA, white colour (28049P), IP54 protection (according to EN 60529)

 

Internal: polyamide, natural colour, IP44 protection (according to EN 60529)

 

Operating ambient conditions:

 

temperature: 0—40 °C

 

rel. humidity: 5—95 % rH (non-condensing)

STANDARDS

 

Low Voltage Directive 2014/35/EU 

 

 EN 60529:1991 Degrees of protection provided by enclosures (IP Code) 
Amendment AC:1993 to EN 60529

 

  EN 60730-1:2011 Automatic electrical controls for household and similar use - 

Part 1: General requirements

 

EMC directive 2014/30/EU:

 

  EN 60730-1:2011 Automatic electrical controls for household and similar use - 

Part 1: General requirements

 

  EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic 

standards - Immunity for residential, commercial and light industrial 
environments

 

  EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic 

standards - Emission standard for residential, commercial and light-industrial 
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3

Summary of Contents for SDX-DM Series

Page 1: ...SDX DM ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions ...

Page 2: ...ROLLER Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 ...

Page 3: ...product performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always dis...

Page 4: ...ed output to motor Umin Us Minimum and maximum output voltage are adjustable via Modbus RTU communication Vmin 20 70 of Us and Vmax 75 100 of Us Overheating protection Operating mode selectable via Modbus RTU from low to high speed or from high to low speed Enclosure External ASA white colour 28049P IP54 protection according to EN 60529 Internal polyamide natural colour IP44 protection according t...

Page 5: ...en output overwrite is enabled the desired output value can be written in Modbus Holding register 13 In that case it is advisable also to activate Modbus safety timeout by writing a value different from 0 in Holding register 8 After the time out period elapses the output is forced to the minimum output value If timeout is set to zero this function is disabled ATTENTION Overheating protection is ac...

Page 6: ...ove the cover of the external enclosure 4 Do the wiring according to the wiring diagram see Fig 1 Wiring and connections 5 Mount the internal enclosure into the wall according to the mounting dimensions shown in Fig 2 Mounting dimensions inset mounting Fig 1 Wiring and connections Power Supply 230 VAC 50 60 Hz Regulated output to motor Modbus RTU communication Fig 2 Mounting dimensions Inset mount...

Page 7: ...the surface by means of the screws and dowels adhering to the mounting dimensions shown in Fig 3 Mounting dimensions surface mounting Fig 3 Mounting dimensions surface mounting 64 64 82 89 63 5 82 Correct Incorrect 5 Insert the cables through the grommets 6 Do the wiring according to the wiring diagram see Fig 1 Wiring and connections 7 Insert the internal enclosure into the external one and fix i...

Page 8: ...he controller is not overheated the Modbus communication is available all connections are correct the machine to be regulated is functioning TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relie...

Reviews: