www.sentera.eu
MIW-RMFPX-2R-EN-000 - 23 / 04 / 2018
5 - 11
■
EMC Directive 2014/30/EC;
►
EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements
►
EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards - Immunity for residential, commercial and light industrial environments
EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commercial and light-industrial
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3
►
EN 61326-1:2013 Electrical equipment for measurement, control and laboratory
use - EMC requirements - Part 1: General requirements
►
EN 61326-2-3:2013 Electrical equipment for measurement, control and
laboratory use - EMC requirements - Part 2-3: Particular requirements - Test
configuration, operational conditions and performance criteria
■
WEEE 2012/19/EC
■
RoHs Directive 2011/65/EC
OPERATIONAL DIAGRAMS
AO1, max
range
AO1, min
range
60
40
100
0
rH Min range
0
5
0 CO
2
Min range
CO
2
Max range
Max
Min
T Min
range
T Max
range
rH Max range
AO1 [%]
50
85
2.000
rH [%]
T [°C]
CO
2
[ppm]
Note:
The output changes automatically depending on the highest T, rH or CO
2
values, i.e. the highest of three output values controls the output. See the green line
in the operational diagram above.
WIRING AND CONNECTIONS
Article type
RMFPF-2R
RMFPG-2R
VIN
18—34 VDC
18—34 VDC
15—24 VAC ±10%
GND
Ground
Common ground
*
AC ~
*
A
Modbus RTU (RS485), signal A
/B
Modbus RTU (RS485), signal /B
AO1
Analog / modulating output - T, rH or CO
2
(0—10 VDC / 0—20 mA / PWM)
GND
Ground AO
Common ground
*
Connections
Spring contact terminal blocks, cable cross section: 1,5 mm
2
* Caution: Never connect the common ground of G type articles to other devices powered by a DC voltage. If an AC power supply is used with a unit on a Modbus
network, the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT-USB-RS485 converter. This may cause permanent damage to
the communication semiconductors and / or the computer!
RMFPX-2R
MULTIFUNCTIONAL
ROOM CONTROLLER