www.sentera.eu
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
10 - 11
HOLDING REGISTERS
Data type
Description
Data
Values
1
Device slave address
unsigned int
Modbus device address
1—247
default: 1
2
Modbus baud rate
unsigned int
Modbus communication baud rate
0—6
default: 2
0 = 4.800
1 = 9.600
2 = 19.200
3 = 38.400
4 = 57.600
5 = 115.200
6 = 230.400
3
Modbus parity
unsigned int
Parity check mode
0— 2
default: 1
0 = 8N1
1 = 8E1
2 = 8O1
4
Device type
unsigned int
Device type. Read only
RMFPМ-2R = 1.611
5
HW version
unsigned int
Hardware version of the device. Read only
XXXX
0x0200 = HW version 2.0
6
FW version
unsigned int
Firmware version of the device. Read only
XXXX
0x0200 = FW version 2.0
7—8
Reserved, return 0
9
Modbus network
resistor termination
(NBT)
unsigned int
Set device as end device of the line / or not by
connecting NBT
0—1
default: 0
0 = NBT disconnected
1 = NBT connected
10
Modbus registers
reset
unsigned int
Resets Modbus Holding registers to default values. When
finished this register is automatically reset to '0'
0—1
default: 0
0 = Idle
1 = Reset Modbus
Registers
11
Minimum temperature
range
unsigned int
Minimum value of temperature range, cannot be set
higher than maximum temperature range minus 5°C
0—Max-50
default: 0
100 = 10,0°C
12
Maximum
temperature range
unsigned int
Maximum value of temperature range, cannot be set less
than minimum temperature range plus 5°C
Min+50—500
default: 500
500 = 50,0°C
13
Minimum temperature
alert
unsigned int
Minimum temperature alarm value
Min. temperature range—Max.
temperature alarm
default: 0
500 = 50,0°C
14
Maximum
temperature alert
unsigned int
Maximum temperature alarm value
Min. temperature alarm—Max.
temperature range
default: 500
500 = 50,0°C
15—18
Reserved, return 0
19
Minimum relative
humidity range
unsigned int
Minimum value of relative humidity range, cannot be set
higher than maximum relative humidity range minus 5%
0—Max-50
default: 0
200 = 20,0 % rH
20
Maximum relative
humidity range
unsigned int
Maximum value of relative humidity range, cannot be set
less than minimum relative humidity range plus 5%
Min+50—1.000
default: 1.000
850 = 85 % rH
21
Minimum relative
humidity alert
unsigned int
Minimum relative humidity alarm value
Min. relative humidity range—
Max. relative humidity alarm
default: 0
200 = 20,0 % rH
22
Maximum relative
humidity alert
unsigned int
Maximum relative humidity alarm value
Min. relative humidity alarm—
Max. relative humidity range
default: 1.000
850 = 85 % rH
23
Minimum CO2 range
unsigned int
Minimum CO2 range, cannot be set higher than
maximum CO2 range minus 100 ppm
0—Max-100
default: 400
1.000 = 1.000 ppm
24
Maximum CO2 range unsigned int
Maximum CO2 range, cannot be set less than minimum
CO2 range plus 100 ppm
Min+100—2.000
default: 2.000
2.000 = 2.000 ppm
25
Minimum CO2 alert
unsigned int
Minimum CO2 alarm value
Min. CO2 range—Max. CO2
alarm
default: 400
400 = 400 ppm
26
Maximum CO2 alert
unsigned int
Maximum CO2 alarm value
Min. CO2 alarm —Max. CO2
range
default: 2.000
2.000 = 2.000 ppm
27—34
Reserved, return 0
38
Minimum output
value
unsigned int. Sets minimum value of output signal expressed as a
percentage
0—40
0
39
Maximum output
value
unsigned int. Sets maximum value of output signal expressed as a
percentage
60—100
100
35
Active mode light
level
unsigned int
The ambient light level above which 'Active' is indicated
in input register 42
0—32.000
default: 100
100 = 100 lux
36
Standby mode light
level
unsigned int
The ambient light level below which 'Standby' is
indicated in input register 42
0—32.000
default: 10
10 = 10 lux
37—39
Reserved, return 0
40
CO2 module self
calibration
unsigned int
Enables or disables the CO2 module self calibration
technique. If enabled it is advisable that the CO2
concentration drops to outside level (400 ppm) in a 7
day period.
0—1
default: 1
0 = Disabled
1 = Enabled
41—44
Reserved, return 0
45
Minimum output
value
unsigned int
Set minimum value of output signal in percentage
0—40
default: 0
20 = 20 %
46
Maximum output
value
unsigned int
Set maximum value of output signal in percentage
60—100
default: 100
60 = 60 %
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER