PRODUCT DESCRIPTION

MDB-M/6 is a compact PoM distribution box. It is suitable for power and data 
distribution between connected units and compatible with transmitters, intelligent 
sensors, sensor controllers, HVAC controllers, fan speed controllers and all other 
Sentera products with Modbus RTU communication.

ARTICLE CODES

Article code

Supply

Imax

Connection type

MDB-M-6

24 VDC (PoM)

1,5 mA

RJ45

INTENDED AREA OF USE

 

Distribute power and data between Modbus RTU compatible units

TECHNICAL DATA

 

Supply voltage: 24 VDC (Power over Modbus)

 

Total I/O current rating: Imax 1,5 A

 

RJ45 connectors for Power over Modbus communication and power supply

 

Surface mountable

 

Maximum total cable length: up to 100 meters

 

Easy to install

 

Reduces installation and equipment costs

 

Protection class: IP65

 

Enclosure: ABS plastic, colour: grey (RAL7035)

 

Storage temperature: -40—85 °C

 

Operating ambient conditions: 

 

temperature range: -30—70 °C

 

rel. humidity: 20—90 % rH (non-condensing)

STANDARDS

 

Low Voltage Directive 2014/35/EU 

 

 EN 60664-1:2007 Insulation coordination for equipment within low-voltage 
systems - Part 1: Principles, requirements and tests

 

EMC Directive 2014/30/EU

 

 

EN 55022:2010 Information technology equipment - Radio disturbance 
characteristics - Limits and methods of measurement Amendment AC:2011 to 
EN 55022:2010 

 

 EN 55024:2010 Information technology equipment - Immunity characteristics - 
Limits and methods of measurement

 

 EN 61000-3-2:2014 Electromagnetic compatibility (EMC) - Part 3-2: Limits - 
Limits for harmonic current emissions (equipment input current ≤ 16 A per phase)

 

 EN 61000-3-3:2013 Electromagnetic compatibility (EMC) - Part 3-3: Limits 
- Limitation of voltage changes, voltage fluctuations and flicker in public low-
voltage supply systems, for equipment with rated current <= 16 A per phase and 
not subject to conditional connection supply systems, for equipment with rated 
current <= 16 A per phase and not subject to conditional connection

 

WEEE Directive 2012/19/EU

 

RoHs Directive 2011/65/EU

POWER OVER MODBUS 
DISTRIBUTION BOX

MDB-M-6

Summary of Contents for MDB-M-6

Page 1: ...Mounting and operating instructions MDB M 6 POWER OVER MODBUS DISTRIBUTION BOX ...

Page 2: ...CAUTIONS 3 PRODUCT DESCRIPTION 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 WIRING AND CONNECTIONS 4 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION 6 TRANSPORT AND STORAGE 6 WARRANTY AND RESTRICTIONS 6 MAINTENANCE 6 POWER OVER MODBUS DISTRIBUTION BOX MDB M 6 ...

Page 3: ...nvironment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecti...

Page 4: ...ng ambient conditions temperature range 30 70 C rel humidity 20 90 rH non condensing STANDARDS Low Voltage Directive 2014 35 EU EN 60664 1 2007 Insulation coordination for equipment within low voltage systems Part 1 Principles requirements and tests EMC Directive 2014 30 EU EN 55022 2010 Information technology equipment Radio disturbance characteristics Limits and methods of measurement Amendment ...

Page 5: ...f the connected units have a different Power supply only crimp the data wires pins 3 4 5 6 in the RJ45 connectors See Wiring and Connections MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the unit read carefully Safety and Precautions Choose a smooth surface for installation a wall panel etc Follow these steps 1 Unscrew the front cover of the enclosure to remove it 2 Fix the enclosure on...

Page 6: ...s 1 2 7 and 8 connected to different Power supplies If the connected units have a different Power supply only crimp the data wires pins 3 4 5 6 in the RJ45 connectors See Wiring and Connections VERIFICATION OF INSTALLATION When the green LED on the left of each RJ45 socket is on supply voltage is detected see Fig 4 below Fig 4 Power indication ATTENTION The maximum power supply per channel must no...

Page 7: ...e the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions these controllers are maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnected from the main supply Pay attention that no...