ATTENTION

The -F version of the product is not suited for 3-wire connection. It has separate 
grounds for power supply and analogue output. Connecting both grounds together 
might result in incorrect measurements. Minimum 4 wires are required to connect 
-F type sensors.
The -G version is intended for 3-wire connection and features a ‘common ground’. 
This means that the ground of the analogue output is internally connected with 
the ground of the power supply. For this reason, -G and -F types cannot be used 
together on the same network. Never connect the common ground of -G type 
articles to other devices powered by a DC voltage. Doing so might cause permanent 
damage to the connected devices.

MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the unit, read carefully 

Safety and Precautions”

Choose a smooth surface for installation (a wall, panel, etc.) and follow these steps:

1. 

Unscrew the front cover of the enclosure to remove it.

2. 

 Fix the enclosure onto the surface by means of suitable fasteners while adhering 
to the mounting dimensions shown in 

Fig. 1

 

and the correct mounting position 

shown in 

Fig. 2

 below.

Fig. 1 Mounting dimensions

Fig. 2 Mounting position

HPD

+ _

80

65

85

2x Ø 6

46

24

20

15

10,5

2x Ø 3,

4

49

52

Correct

Incorrect

HPD

+ _

HPD

+

_

HPD

+

_

3. 

Insert the cable into the cable gland. 

4. 

 Connect as shown in 

Fig. 3

 

Connections

 adhering to the information in section 

Wiring and connections

”.

Fig. 3 Wiring and connections

GND

GND

GND

/B

Vin

A

AO1

AO2

5. 

 Switch on the power and perform a calibration procedure (refer to section 
“OPERATING INSTRUCTIONS”) .

6. 

 Connect the nozzles to the duct (see 

Fig. 4

). Depending the application you must 

use a specific connection set to connect the nozzles of the unit to the duct: 

6.1 

 To measure differential pressure, use PSET-QF or PSET-PVC set (pressure 
measurement is the unit default setting).

DUAL DIFFERENTIAL 
PRESSURE TRANSMITTER 

HPD

Summary of Contents for HPD

Page 1: ...Mounting and operating instructions HPD DUAL DIFFERENTIAL PRESSURE TRANSMITTER ...

Page 2: ...ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 8 OPERATING INSTRUCTIONS 9 TRANSPORT AND STORAGE 10 WARRANTY AND RESTRICTIONS 10 MAINTENANCE 10 DUAL DIFFERENTIAL PRESSURE TRANSMITTER HPD ...

Page 3: ...e work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before ...

Page 4: ...nt by using an external PSET PTX 200 Pitot tube connection set in HVAC applications Differential pressure volume flow monitoring in clean rooms Clean air and non aggressive non combustible gases TECHNICAL DATA 2 built in digital high resolution differential pressure sensors Air velocity can be measured via Modbus RTU by using an external PSET PTX 200 Pitot tube connection set 2 selectable analogue...

Page 5: ...ective 2012 19 EC RoHs Directive 2011 65 EC OPERATIONAL DIAGRAM 0 10 20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100 VDC mA PWM Output Differential Pressure Range Pa Control range Minimum Control range Maximum WIRING AND CONNECTIONS Article type HPD F HPD G Vin 18 34 VDC 18 34 VDC 13 26 VAC Ground Common ground AC GND Ground AC A Modbus RTU RS485 signal A B Modbus RTU RS485 signal B AO1...

Page 6: ...oose a smooth surface for installation a wall panel etc and follow these steps 1 Unscrew the front cover of the enclosure to remove it 2 Fix the enclosure onto the surface by means of suitable fasteners while adhering to the mounting dimensions shown in Fig 1 and the correct mounting position shown in Fig 2 below Fig 1 Mounting dimensions Fig 2 Mounting position HPD _ 80 65 85 2x Ø 6 46 24 20 15 1...

Page 7: ...led and Pitot tube connected 6 3 To measure air velocity use PSET PT set and enable Pitot tube air velocity via holding register 64 for sensor module 1 or in holding register 84 for sensor module 2 In this case the K factor of the fan has to be 0 Fig 4 Connecting with accessories Application 1 Measuring differential pressure Pa or volume flow m h using PSET PVC Application 2 Measuring volume flow ...

Page 8: ... Example 1 Example 2 RX ТX NBT NBT Slave 2 Master Slave n Slave 1 Slave 2 Slave 1 RX ТX NBT NBT Master Slave n NOTE On a Modbus RTU network two bus terminators NBTs need to be activated 9 Put back the front cover and secure it with the screws 10 Customise the factory settings to the desired ones via the 3SModbus software or the Sensistant configurator For the default factory settings see Modbus re...

Page 9: ... indication 1 3 After the calibration is done the blue LED3 will blink twice once again to indicate that the calibration procedure has finished 2 Sensor module 2 2 1 Disconnect the nozzles and make sure they are not clogged 2 2 There are two options for starting the calibration process Either write 1 in holding register 90 or press tact switch SW2 for about 5 seconds until the blue LED4 on the pri...

Page 10: ...ditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance fr...

Reviews: