www.sentera.eu
MIW-HPD-X-EN-001 - 19 / 03 / 2020
6 - 10
ATTENTION
The -F version of the product is not suited for 3-wire connection. It has separate
grounds for power supply and analogue output. Connecting both grounds together
might result in incorrect measurements. Minimum 4 wires are required to connect
-F type sensors.
The -G version is intended for 3-wire connection and features a ‘common ground’.
This means that the ground of the analogue output is internally connected with
the ground of the power supply. For this reason, -G and -F types cannot be used
together on the same network. Never connect the common ground of -G type
articles to other devices powered by a DC voltage. Doing so might cause permanent
damage to the connected devices.
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the unit, read carefully
“
Safety and Precautions”
.
Choose a smooth surface for installation (a wall, panel, etc.) and follow these steps:
1.
Unscrew the front cover of the enclosure to remove it.
2.
Fix the enclosure onto the surface by means of suitable fasteners while adhering
to the mounting dimensions shown in
Fig. 1
and the correct mounting position
shown in
Fig. 2
below.
Fig. 1 Mounting dimensions
Fig. 2 Mounting position
HPD
+ _
80
65
85
2x Ø 6
46
24
20
15
10,5
2x Ø 3,
4
49
52
Correct
Incorrect
HPD
+ _
HPD
+
_
HPD
+
_
3.
Insert the cable into the cable gland.
4.
Connect as shown in
Fig. 3
Connections
adhering to the information in section
“
Wiring and connections
”.
Fig. 3 Wiring and connections
GND
GND
GND
/B
Vin
A
AO1
AO2
5.
Switch on the power and perform a calibration procedure (refer to section
“OPERATING INSTRUCTIONS”) .
6.
Connect the nozzles to the duct (see
Fig. 4
). Depending the application you must
use a specific connection set to connect the nozzles of the unit to the duct:
6.1
To measure differential pressure, use PSET-QF or PSET-PVC set (pressure
measurement is the unit default setting).
DUAL DIFFERENTIAL
PRESSURE TRANSMITTER
HPD