PRODUCT DESCRIPTION

The DTP-M series are digital temperature water pipe sensors powered over Modbus 
with 24 VDC via an RJ45 connector. They are intended for mounting onto metal 
pipes and are compatible with various temperature control systems. Thanks to the 
copper contact plate, we can ensure fast response times and faster response time 
and a more accurate temperature measurement of the media within the pipe.  

ARTICLE CODES

Code

Power supply

Imax

DTP-M

24 VDC, PoM

8 mA

INTENDED AREA OF USE

 Measuring temperature in metal water pipes

TECHNICAL DATA

 

Sensor range: 0—85 °C

 

Modbus RTU communication

 

Easy wiring via an RJ45 socket

 

Quick and easy mounting via a cable tie

 

Copper plate for enhanced thermal conductivity

 

Heat resistant cable tie 300 x 4,8 mm included

 

 Thermal pad for a more accurate temperature measurement included (19 x 14 x 
1,5 mm)

 

Supply voltage: 24 VDC, Power over Modbus

 

Protection standard: IP65

 

Operating ambient conditions: 

 

temperature: -30—85 °C

 

rel. humidity: 5—95 % rH (non-condensing)

STANDARDS

 

EMC directive 2014/30/EU: 

 

 

 EN 61326-1:2013 Electrical equipment for measurement, control and laboratory 
use - EMC requirements - Part 1: General requirements

 

 

EN 61326-2-3:2013 Electrical equipment for measurement, control and 
laboratory use - EMC requirements - Part 2-3: Particular requirements - Test 
configuration, operational conditions and performance criteria for transducers 
with integrated or remote signal conditioning

 

 

EN 61326-2-5:2013 Electrical equipment for measurement, control and 
laboratory use - EMC requirements - Part 2-5: Particular requirements - Test 
configurations, operational conditions and performance criteria for devices with 
field bus interfaces according to IEC 61784-1 

 

WEEE Directive 2012/19/EC

 

RoHs Directive 2011/65/EC

DTP-M 

DIGITAL TEMPERATURE PIPE SENSOR

Summary of Contents for DTP-M

Page 1: ...Mounting and operating instructions DTP M DIGITAL TEMPERATURE PIPE SENSOR ...

Page 2: ...PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 WIRING AND CONNECTIONS 5 MOUNTING OPERATING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION 7 TRANSPORT AND STORAGE 7 WARRANTY AND RESTRICTIONS 7 MAINTENANCE 7 DTP M DIGITAL TEMPERATURE PIPE SENSOR ...

Page 3: ...onment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting s...

Page 4: ... 8 mm included Thermal pad for a more accurate temperature measurement included 19 x 14 x 1 5 mm Supply voltage 24 VDC Power over Modbus Protection standard IP65 Operating ambient conditions temperature 30 85 C rel humidity 5 95 rH non condensing STANDARDS EMC directive 2014 30 EU EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requir...

Page 5: ...2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 3 4 5 6 3 4 MOUNTING OPERATING INSTRUCTIONS IN STEPS Before you start mounting the unit read carefully Safety and Precautions Follow these steps 1 Remove the rubber cap of the unit and mount the unit onto the pipe outer surface via placing the thermal pad between the copper plate and the pipe 2 Secure the unit using the cable tie included in the set as shown in Fig 1 ...

Page 6: ...ault factory setting refer to the product Modbus register map 5 For the complete Modbus register data refer to the product Modbus Register Map which is a separate document attached to the article code on the website and contains the registers list Products with earlier firmware versions may not be compatible with this list NOTE Optional settings To assure correct communication the NBT needs to be ...

Page 7: ...ginal packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean w...

Reviews: