background image

“INTERCONNCT” (orange) wire.

 If doing so, it will damage the detector. 

 

7. Line up the slot of the bracket and the detector. Push the detector onto the 

mounting bracket and turn it clockwise to fix it  into place. Pull outward  on 
the detector to make sure it is securely attached to the mounting bracket. 

 

 
8. The steps to open the battery cover and to install the battery are listed as 

follows: 

(1)To power Smoke detector 
requires an alkaline battery. 
(2)Match terminals on the end(s) of 
the  battery  with  opposite  terminal 
connections  on  the  detector.  Be 
sure to insert the alkaline battery in 
the position shown on the detector. 

(3)

When  terminals  are  properly 

matched, push battery firmly in until 
it  snaps  and  cannot  be  shaken 
loose. 

IMPORTANT: For the AC powered model- Whenever placing 
or  removing  battery  in  the  detector,  try  to  disconnect  AC 
power  at  the  fuse  box  or  circuit  breaker  to  avoid  electrical 
shock hazard. 

CAUTION:

 

This smoke detector comes with cover latches that will 

prevent  the  smoke  detector  cover  from  closing  if  battery  is  not 
installed. This tells you that the smoke detector will not work until a 
new  battery  is  properly  installed. 

The  battery  is  purposely 

positioned  WRONGLY  in  the  factory  to  keep  it  fresh  until 
installation. It must be  re-positioned  correctly  to  provide  DC 
power.

 

NOTE:

 

When  the  detector  battery  first  makes  contact  with  the 

detector, the alarm  horn may sound for  one second.  This  means 
normal and indicates that the battery is positioned properly. Close 
cover,  then  press  the  test  button,  holding  it  down  for  about  5 
seconds  until  the  horn  sounds.  The  horn  should  sound  a  loud, 
pulsating alarm. This means the unit is working properly. 

 

HOW TO INTERCONNECT MODEL SD-218*-I 
DETECTORS TOGETHER 

Warning:

  Failure  to  follow  the  installation  instructions  below  could  result  in 

malfunction and damage to the detector.   

The SD-218 series with I mark smoke detectors means with "interconnection" 
capability may be  connected  together.  Then,  if  one  detector  senses  smoke, 
all of them will  sound  their alarms. The  following  conditions  must  be  met  to 
ensure the interconnected detectors working properly: 

(1) The SD-218 series with I mark smoke detector can be interconnected 
only to other detectors of the same type. 

DO NOT

 connect to any other type 

or model smoke alarm.

 

 

(2) The  SD-218  series  with  I  mark  smoke  detectors  may  be  interconnected 

with as many as 38 other detectors. 

  (3) 

The  total  length  of  wire  interconnecting  the  detectors  should  be  no 

more  than  1000  feet.  The  interconnecting  wire  should  be  #18  AWG  or 
larger and be rated at least 300V. 

(4) The  installation  of  such  detector  must  be  in  accordance  with  the 

requirements of Article  760  of the National Electrical  Code and any  local 

codes that apply. 

(5) Wire  the  interconnection  type  detectors  by  connecting  the  interconnect 

connectors on all units together. See figure 9. 

(6) Be sure the batteries are properly installed for each detector. 

(7) To test the system,  push  test button  on  each  detector.  The  alarm  horns 

on  all  of  the  detectors  in  the  system  should  sound  if  they  are 
interconnected  correctly.  Make  sure  that  all  other  units  in  the  system 
sound an alarm as each unit  is  tested.  Interconnect  the  detectors  within 
one family residence area only. Otherwise,   

when a detector  in  another  residence  is  tested,  the  occurrence  of  nuisance 
alarms may take place. 

 

 

 

 

 

Figure  9.A:  WIRING  DIAGRAM  FOR  INTERCONNECTION  MODEL 
SD-218 series with I mark   
 
 

 

 

 

 

Figure  9.B:  WIRING  DIAGRAM  FOR  INTERCONNECTION  MODEL 
SD-218-A series with I mark 

 

 

 

RED INDICATOR 

The red LED, as the ALARM indicator, is featured with the detector. It can be 
seen  through  the  test  button  on  the  cover  of  the  detector.  When  red  LED 
flashes  once  32  seconds,  it  indicates  the  detector  under  normal  operation. 
When smoke detector senses smoke and simultaneously sounds an audible 
alarm,  the  red  LED  will  flash  very  frequently,  once  0.67  seconds.  For  the 
interconnected system, whereas the red LED does  not light, it  indicates that 
the  other  detector(s)  belonging  to  the  same  interconnection  system  has 
sensed smoke and is signaling the alarm. 
 
 

TESTING YOUR SMOKE DETECTOR

 

Test the detector weekly by pushing firmly on the test button with your  finger 
until the  horn sounds. Testing method may take  up  to  20  seconds  to  sound 
the  alarm  horn.  These  are  only  ways  to  be  sure  that  detector  is  working 
correctly.  If  the  detector  fails  to  test  properly,  have  it  repaired  or  replaced 

TO  ADDITIONAL  DETECTORS 
MAX. OF 38 INTERCONNECTED 

Battery 

Cover 

NOTES FOR INTERCONNECTION: 

  Brown to Hot (Live) 

  Blue to Neutral   

  Orange to Interconnection 

NOTES FOR NON-INTERCONNECTION AC MODELS, THERE’S NO “ORANGE” 
WIRE, PLEASE CONNECT ONLY BLUE AND BROWN WIRES. 

  Brown to Hot (Live) 

  Blue to Neutral 

NOTES FOR INTERCONNECTION: 

  Blue to Ground 

  Orange to Interconnection 

 

TO  ADDITIONAL  DETECTORS 
MAX. OF 38 INTERCONNECTED 

Summary of Contents for SD-218-A Series

Page 1: ...al units smoke detectors should be installed in all rooms halls storage areas basements and attics in each family living unit Minimum coverage is one detector on each floor and one in each sleeping area and attics in each family living unit Minimum coverage is one detector on each floor and one in each sleeping area Here we have useful tips for you Install a smoke detector in the hallway outside e...

Page 2: ...ding unheated buildings or outdoor rooms If the temperature goes above or below the operating range of smoke detector it will not work properly The temperature range for your smoke detector is 32 o F to 120 o F 0 o C to 50 o C In very dusty or dirty areas dirt and dust can build up on the detector s sensing chamber to make it overly sensitive Additionally dust or dirt can block openings to the sen...

Page 3: ...series with I mark smoke detectors may be interconnected with as many as 38 other detectors 3 The total length of wire interconnecting the detectors should be no more than 1000 feet The interconnecting wire should be 18 AWG or larger and be rated at least 300V 4 The installation of such detector must be in accordance with the requirements of Article 760 of the National Electrical Code and any loca...

Page 4: ...ature between 132ºF and 180 ºF This requirement can be met by some domestic hair dryers Proceed as follows 1 Switch on the warm air flow and check that temperature is correct and stable 7 2 From a distance of inches direct the airflow at the guard protecting the thermistor The detector should alarm within 30 seconds 3 On alarm immediately remove the heat source check that the detector s red LED is...

Reviews: