background image

z

 

CAUTIONS 

This heat detector is particularly designed to 

initiate and 

activate 

emergency action, but will do so only when it is 

used in conjunction with an authorized fire alarm system. 
This detector must be installed in accordance with NFPA 
Standard 72. 

The purpose of design of heat detectors is meant to 
protect property, not life.

 The heat detectors do not provide 

early warning of fire and cannot detect smoke, gas, 
combustion particles, or flame. They will alarm when 
temperature at the heat detector reach 57

o

C (135

o

F) or 

above. Given the rapid growth of certain types of fires, heat 
detectors cannot be expected to provide adequate warning 
of fires resulting from smoking in bed, inadequate fire 
protection practices, violent explosions, escaping gas, and 
improper storage of flammable liquids like cleaning solvents, 
other safety hazards, or arson. 

Heat detectors do not always detect all fires because the 
fire may be a slow-smoldering, low-heat type (producing 
smoke), or because they may not be mean where the fire 
occurs, or because the heat of the fire may bypass them.

 

Heat detectors will not detect smoke, gas, flames, or 
combustion particles. 
Heat detectors are components in professionally installed fire 
alarm systems. 

They will not function if they have been 

improperly wired into the fire alarm system or if power to 
them is disconnected for any reason. 
Heat detectors cannon last forever. 

They should be tested 

and maintained following the instructions in this manual. To 
be safe, they should be replaced after they have been 
installed for ten years. 
Refer to NFPA 72 for application. 

Maintenance 

At least once every 12 months remove the detector for close 
inspection and, if found to be necessary cleaning, clean the 
detector more frequently if environment contains appreciable 

sources dirt or corrosive agents. 

IMPORTANT

Before removing a detector for maintenance, 

notify the appropriate authorities that fire alarm system or a 
specific zone of the system will be temporarily out of service. 
Disable the zone or system undergoing maintenance to prevent 
unwanted alarms.   

To maintain a heat detector the following steps can be 
applied: 

1.      Remove the detector head from its base. 
2.    Do not damage the heat sensor for the heat detector 

models. 

3.    Check that thermistor bead is free from dirt or dust, if 

necessary; gently wipe it with a clean tissue paper. 

4.    After cleaning the detector, be sure not to tangle the 

leads of thermistor. 

5.   Check thermistor head in standing upright in the 

center of its plastic protective guard. 

6.    Install the detector into its base again. 
7.      Test the operation of the heat detector. 
8.   Enable the zone or system again and notify the 

appropriate authorities that the maintenance 
operation is complete and the system is active again. 

9.  Enable the zone or system again and notify the 

appropriate authorities that the maintenance 
operation is complete and the system is active again. 

Heat detectors are designed to be as maintenance-free as 
possible. However, dirt or corrosive agents can accumulate 
inside a detector’s sensing head and influence its sensitivity. 
They could reduce the amount of warning time given in case 
of a fire.    Therefore, detectors should be tested periodically 
and maintained at regular intervals. Follow closely the 
manufacturer’s recommended procedures for maintenance 
and testing and refer to the NFPA 72. 

REFER TO THE TECHNICAL BULTTIN ISSUE NO. STHD20080508S1, 
REV.E, May 08, 2008. 

 
SPECIFICATION 

Model 

2/4  

wire 

Voltage 

DC 

Standby

Current

(Max) 

Alarm 

Current 

(Min /Max) 

Surge 

Current 

(Max) 

Frequency

Temperature

Rating 

 

Rate of Rise of 

Temperature

(Max) 

UL Maximum

Spacing 

(10-foot ceiling)

Alarm 

Impedance 

(Min/Max) 

Alarm 

Contact 

Base 

 Model

HD 912-2 

10.8~33V  180

μ

A

18/80mA 180

μ

A 1-3 

Seconds

13

5 ℉/57 ℃

1

5 ℉/8.3 ℃

40-feet x40-feet

411

/594

 - 

P/N852001

HD 912-2L 

10.8~33V  180

μ

A

18/80mA 180

μ

A 1-3 

Seconds 13

5 ℉/57 ℃

1

5 ℉/8.3 ℃

40-feet x40-feet

411

/594

 - 

P/N854001

HD 912-4(12V) 

12V 

180

μ

A

23/33mA 180

μ

A 1-3 

Seconds

13

5 ℉/57 ℃

1

5 ℉/8.3 ℃

40-feet x40-feet

Form A 

P/N854001

HD 912-4(24V) 

24V 

180

μ

A

34/46mA 180

μ

A 1-3 

Seconds

13

5 ℉/57 ℃

1

5 ℉/8.3 ℃

40-feet x40-feet

Form A 

P/N854001

 

Remarks:

 

L

-remote LED indicator output 

 

 

 

 

HDMI912080528, REV H, 05.28.2008.

   

 

LIMITED WARRANTY STATEMENT 

SENTEK ELECTRONICS INC. 

declares that this product is free from defects in material and workmanship. And it will repair or replace 

any product or part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from the date of 
purchase but not to exceed eighteen (18) months after shipment by the manufacturer. For a full description of SENTEK

S LIMITED 

WARRANTY, which, among other things, limits the duration of warranties of merchantability and fitness for a particular purpose and 
excludes liability for consequential damages. Please read the entire LIMITED WARRANTY on the SENTEK quotation. Acceptance of order 
and/or original invoice which will become part of your sales agreement. Please contact SENTEK directly for a return merchandise 
authorization (RMA) number before returning goods to the factory . Shipment must be prepaid and SENTEK will repair or replace your 
returned detector

Reviews: