background image

1.  Using a #2 Phillips screwdriver, 

attach the provided mounting feet to 

the four corners of the back of the 

unit using the provided screws. (Fig. 

9). The feet can be attached either 

horizontally or vertically according 

to preference.

2.  Mark the location on the wall where 

you want to mount the unit. If you 

mounted the feet horizontally, the 

x axis markings should be 17 cm 

apart and the y axis markings 

should be 7.5 cm apart. If you 

mounted the feet vertically, the 

x axis markings should be 12.5 

cm apart and the y axis markings 

should be 12 cm apart.

3.  Mount the unit to the wall using the 

open side of the mounting feet and 

appropriate sized screws.

Wall Mount 

Fig. 9: Attach mounting feet

Please Note

The FCC etching on the top of the outside enclosure exterior cannot be obstructed from view.  

When planning where to mount the Smart Gateway, ensure that the FCC etching is visible and 

readable from all perspectives.

1.  Run the customer provided clamps 

through the Sensus provided 

mounting bars (Fig. 10).

2.  Using a #2 Phillips screwdriver, 

attach one of the provided mounting 

bars, with clamp installed, to the 

back of the unit using the provided 

screws.

3.  Repeat for the second mounting bar 

and band/hose clamp.

4. Attach the unit to the pipe using 

the band/hose clamps. You can 

mount the unit to a horizontal or 

vertical pipe (Fig. 11 shows the unit 

mounted to a vertical pipe).

Pipe Mount

Fig. 10: Pipe mount bars and clamps

Fig. 11: Attach 

to pipe

AIG-10043-03

Smart Gateway

Installation Guide

Recommendation

If installing on a pipe, Sensus recommends that you install the transducer cable into the pipe 

before wiring it into the Smart Gateway. This will reduce twisting on the transducer cable.

Proper Placement of the CommandLink

For complete instructions on activating the Smart Gateway please refer to the 

FieldLogic Smart Gateway Quick Guide.
1.  Power on your HHD and the Command Link.
2.  Position the CommandLink’s antenna area on the SmartPoint Module’s ASK 

location as shown. This location is at the top of the SmartPoint for the Smart 

Gateway.

3.  Launch FieldLogic Tools.

Summary of Contents for AIG-10043-03

Page 1: ...and through the hole you just punched out Fig 3 in such a way that the gasket is on the outside of the enclosure Tighten the nut on the inside but not the cable gland Fig 4 Note The provided cable gland can accommodate one 1 5 10 mm wire To accommodate additional wires please order the optional multi wire kit from Sensus 3 Run your customer provided transducer cable through the cable gland and int...

Page 2: ...t around the cable and the nut that secures the cable gland to the housing is tightened firmly Close the lid of the module Fig 8 Fig 8 Closed module with cable installed AIG 10043 03 Smart Gateway Installation Guide Fig 7 Pin layout label Fig 6 Attach sensors Sensor Connection If you are using a 2 wire sensor Connect the sensor power to the terminal labeled Sensor Connect the sensor 4 20 mA output...

Page 3: ...mer provided clamps through the Sensus provided mounting bars Fig 10 2 Using a 2 Phillips screwdriver attach one of the provided mounting bars with clamp installed to the back of the unit using the provided screws 3 Repeat for the second mounting bar and band hose clamp 4 Attach the unit to the pipe using the band hose clamps You can mount the unit to a horizontal or vertical pipe Fig 11 shows the...

Page 4: ...ion Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may c...

Reviews: