Sensus 441-S Installation And Maintenance Instructions Manual Download Page 4

failure of the regulator to lock-up. The allowable over 
pressurization is the lowest of the maximum pressures permitted
by federal codes, state codes, Bulletin RDS-1498, or other 
applicable standards. The method of providing over pressure 
protection could be a relief valve, a monitor regulator, a shut off
device or any similar device.

Temperature Limits

The Model 441-S Regulator can be used for flowing temperatures
from -20°F to 150°F.

Buried Service

The Model 441-S Regulator is not recommended for buried service.

Condensed Parts List

For complete parts list and list prices please refer to RP 1350. 
When ordering parts for a 441-S regulator, include pipe size,
model number, inner valve size, and serial number if possible.

Maximum Emergency Pressure

The maximum pressure the Model 441-S regulator inlet may be
subjected to under abnormal conditions without causing damage
to the regulator is 125 psi.

The Maximum pressure the regulator outlet may be subjected to 
without causing damage to the internal part of the regulator is:

10" Diaphragm

set-point + 4 psi

12" Diaphragm

set-point + 3 psi

14" Diaphragm 

set-point + 2 psi

16" Diaphragm

set-point + 1 psi

18" Diaphragm

set-point + 1 psi

20" Diaphragm 

set-point + 1 psi

The set-point is defined as the outlet pressure a regulator is 
adjusted to deliver.

If any of the above pressure limits are exceeded, the regulator 
must be taken out of service and inspected. Damaged or
otherwise unsatisfactory parts must be repaired or replaced. 

The maximum pressure that can be safely contained by the 
diaphragm case is:

10" Diaphragm

15 psi

12" Diaphragm

10 psi

14" Diaphragm

10 psi

16" Diaphragm

5 psi

18" Diaphragm

5 psi

20" Diaphragm

5 psi

Safely contained means no leakage as well as no bursting. Before using
any of the above data, make sure this entire section is clearly understood.

Other Gases 

The Model 441-S is mainly used on natural gas services; however, 
this regulator will perform equally as well on other gases. When
using the Model 441-S Regulator on other gases, the regulator
capacities must be adjusted using the correction factors on page 5.

4

Installation and Maintenance Instructions

Model 441-S Regulator

To Change Spring

1

Remove seal cap 

1

, back off adjusting screw 

10

, remove 

housing cover 

5

, and remove spring 

14

.

2

Insert the new spring. Be sure it nests correctly onto part 

15

.

3

Complete as per steps 7, 8 and 9 under "To Assemble 441-S".    

To Service Diaphragm

1

Remove seal cap 

1

, back off adjusting screw

10

, remove

housing cover 

5

, and remove spring 

14

.

2

Remove bolts 

42

and then carefully remove upper diaphragm

case 

43

.

3

Turn diaphragm assembly counterclockwise until 

24

unscrews

from 

50e

or 

50i

, then remove assembly and inspect 

diaphragm. 

4

If a new diaphragm 

20

is required, remove nut 

16

and 

disassemble.

5

Reassemble diaphragm assembly (parts 

16

17

18

19

20

,

21

22

23

24

). 

6

Screw diaphragm assembly back into place (

24

screws into

50e

or 

50i

until it bottoms) then 

back off 1/2 to 1 full turn  

this is important

.

7

Carefully reinstall upper diaphragm case 

43

. Diaphragm must

not be pinched between upper and lower cases, 

43

and 

40

Tighten bolts 

42

evenly.

8

Replace spring, etc., per steps 6 through 9 under 
“To Assemble 441-S”.

To Assemble 441-S

1

Install orifice 

28

through top opening.

2

Install valve assembly and orifice 

29

per applicable steps 1

through 6 under “To Replace and Adjust Valves” (except that 

50e

or 

50i

does not yet screw into 

24

).

3

Install centerpiece and lower diaphragm case, 

36

and 

40

.

4

Install diaphragm assembly and upper case 

43

per steps 

5 through 7 under “To Service Diaphragm”.

5

Replace bottom plate 

33

. Match bottom end of 

50h

into 

31

and /or 

32

, and then rotate bottom plate either way to first 

matching bolt hole position.

6

Insert the spring. Be sure it nests correctly onto part 

15

.

7

Insert top spring button 

12

. Be sure it is nested correctly 

on the spring.

8

Install housing cover 

5

. Be sure ball 

13

is in place and the

lower end of adjusting screw 

10

goes in the hole in button 

12

.

9

Set adjusting screw 

10

for desired outlet pressure, 

firmly tighten nut 

11

and replace seal cap 

1

.

Over Pressurization Protection

Protection must be provided for the downstream piping system 
and the regulator's low pressure chambers to assure against the
potential over pressurization due to a regulator malfunction or a

Summary of Contents for 441-S

Page 1: ...RM 1350 R7 Sensus Metering Systems Installation and Maintenance Instructions Model 441 S Regulator T H E G A S I N D U S T R Y ...

Page 2: ...e larger size The 1 2 union 60 contains a small orifice approximately 1 16 diameter This orifice should not be removed Also make certain this orifice is open and free of foreign material Check all connections for leaks CAUTION Turn gas on very slowly If an outlet stop valve is used it should be opened first Do not overload the diaphragm with a sudden surge of inlet pressure Monitor the outlet pres...

Page 3: ...a few turns 50e or 50i screws into 24 but should be loose by 1 2 to 1 turn 3 If orifice 29 was removed reinstall it 4 Inset lower valve assembly and screw into place by a few turns 50h screws into 50e 5 Turn upper valve assembly so Allen screw 50g is accessible through side inspection opening 6 Make the valve lock up adjustment as follows a Hold upper valve against its seat This can be done by han...

Page 4: ...usted using the correction factors on page 5 4 Installation and Maintenance Instructions Model 441 S Regulator To Change Spring 1 Remove seal cap 1 back off adjusting screw 10 remove housing cover 5 and remove spring 14 2 Insert the new spring Be sure it nests correctly onto part 15 3 Complete as per steps 7 8 and 9 under To Assemble 441 S To Service Diaphragm 1 Remove seal cap 1 back off adjustin...

Page 5: ...150 20 20 14 Diaphragm 090 72 150 20 16 Diaphragm 090 73 150 20 18 Diaphragm 090 74 150 20 20 Diaphragm 090 75 150 20 23 O Ring 11 16 I D 7 8 O D 934013 24 Diaphragm Connecting Stem 090 16 058 00 stainless steel 41 Hex Steel Nut 3 8 16 920853 42 Hex Cap Screw 3 8 16 x 1 3 8 Lg 903568 45 Travel Indicator Assembly 5 Installation and Maintenance Instructions Model 441 Regulator 2 Model 441 S Illustra...

Page 6: ...0a Valve Retaining Nut 5 8 18 905564 2 and 3 Model 441 S continued Illustration Part Number Description Number Valve Retainer standard steel 1 3 4 090 16 018 00 Valve Retainer standard 090 16 018 30 stainless steel 1 3 4 Valve Retainer v port wings 090 16 012 53 stainless steel 1 3 4 50b Valve Retainer standard steel 090 16 018 01 1 1 2 Valve Retainer standard 090 16 018 31 stainless steel 1 1 2 V...

Page 7: ... plated steel 090 22 028 02 2 1 8 Inlet Orifice stainless steel 090 22 028 52 1 3 4 Inlet Orifice plated steel 090 22 028 01 1 3 4 Inlet Orifice stainless steel 090 22 028 51 3 Outlet Orifice plated steel 090 22 029 00 3 Outlet Orifice stainless steel 090 22 029 50 29 2 1 8 Outlet Orifice plated steel 090 22 029 02 2 1 8 Outlet Orifice stainless steel 090 22 029 52 1 3 4 Outlet Orifice plated stee...

Page 8: ...2 1 2 14 1 2 Flanged ANSI 300 10 1 2 12 1 2 14 1 2 Pipe Size D E G M N of 441 S 2 6 24 See 5 7 3 6 24 Table 5 7 4 9 1 2 26 Below 5 8 Sensus Metering Systems 2007 Made in USA 805 Liberty Boulevard DuBois PA 15801 800 375 8875 Fax 814 375 8460 www sensus com Limited Warranty Seller warrants the Goods to be free from defects in materials manufactured by Seller and in Seller s workmanship for a period...

Reviews: