Sensus 441-57S Installation And Maintenance Instructions Manual Download Page 2

2

T

he Model 441-57S Regulator is an excellent general purpose gas pressure regulator for larger loads. 

Use it for natural gas, air, dry CO

2

, propane, butane, and other gases.

Regulator

Maximum

Body Type

Body Materials

Inlet Pressure

2" Screwed

Cast Iron

250 psi

Flanged ANSI 125 

Cast Iron

175 psi*

Flanged ANSI 250 

Ductile Iron

575 psi*

Flanged ANSI 300 

Cast Steel

720 psi *

Flanged ANSI 600 

Cast Steel

1000 psi*

*Carefully note the following exceptions to the above, based on valve size:

Maximum Inlet Pressures

Maximum 

Body Size

Valve

Inlet Pressure

6"

4-1/4"

150 psi

6"

3" reduced

300 psi

4"

3"

6"

2-1/8" reduced

4"

2-1/8" reduced

500 psi

3"

2-1/8"

Valve material selection is limited by inlet pressure and differential.

Valve

Maximum

Maximum

Material

Inlet Pressure

Pressure Differential

Buna-N

575 psi

250 psi

Poly-U Red

720 psi

400 psi

Poly-U Tan

1200 psi

600 psi

Installation and Start-Up

1.

Thoroughly purge inlet piping to remove dirt and debris 
that could damage the regulator or impair its operation. 
If this cannot be done, a filter or strainer should be installed 
ahead of the regulator (see Catalog RDS 1498, Regulator 
Pressure Ratings). Make certain that inside of regulator and 
piping are free of dirt, foreign matter, and other debris.

2

.

Install the regulator. Make certain flow through the regulator 
is in the correct direction. High pressure connects to 
the inlet side. Be sure that shipping screens or covers, 
if used, are removed. 

On flanges, tighten bolts evenly. On screwed connections, 
apply pipe dope to male threads only.

Where required, the regulator may be inverted.

CAUTION

It is the user’s responsibility to assure that all regulator 
vents and/or vent lines exhaust to a non-hazardous location
away from ANY POTENTIAL sources of ignition. 
Where vent lines are used, it is the user’s responsibility 
to assure that each regulator is individually vented and 
that common vent lines ARE NOT used.

3.

The vent connection is an escape path for flammable gas and 
it must be located and/or piped so that potential discharge 
occurs in a safe area away from buildings, open flames, 
collection areas, arcing devices, etc.

Regulators that are installed indoors or in a non-vented area 
must be vented to the outside. Simply run vent piping from 
the regulator vent connection to a non-hazardous location 
on the outside away from any potential sources of ignition. 
The vent piping must be connection size or larger and piped 
to a safe area.

The outlet of the vent piping must allow for the free and 
unobstructed passage of air and gas and must be protected 
against the potentials listed in the instructions.

4.

For outdoor installations, it is recommended that the 
regulator be installed so that the regulator vent faces 
downward to avoid the potential for water or other foreign 
matter entering the regulator and interfering with proper 
operation of the regulator.

5.

Install the control line. Run it from the Union shown at 

60

on the regulator to the control connection in the outlet piping. 
The control line should be no less than 1/2” in size. It should 
be sturdy with adequate protection against breakage 
(regulators go wide open if the control line is broken). Pitch it 
to drain away from the regulator, free of moisture pockets.
The regulator will work to deliver the pressure (for which it 

is adjusted) at that point in the piping where the control 
connection is located.

In general, the control connection should be at least eight 
pipe diameters downstream from the regulator and should  
be in as straight a run of pipe as possible where turbulence

is at a minimum. Keep clear of elbows, valves, and other 

causes of excessive turbulence.

The control connection should be clean and smooth inside 
the pipe to minimize turbulence. It should be free of rough 
edges, welding “icicles”, etc. It should be located on the top 
or side of the pipe, not on the bottom. Where outlet piping 
increases in size near the regulator, it is generally preferable 
to locate the connection to the larger size piping.
The Union 

60

contains a small orifice (approximately 

1/16” diameter). This orifice should not be removed. 
Also, make certain it is open and free of foreign material.

6

Check all connections for leaks.

Installation and Maintenance Instructions

Model 441-57S Regulator

Summary of Contents for 441-57S

Page 1: ...Models 441 57S Regulator RM 1360 R9 Installation and Maintenance Instructions ...

Page 2: ... occurs in a safe area away from buildings open flames collection areas arcing devices etc Regulators that are installed indoors or in a non vented area must be vented to the outside Simply run vent piping from the regulator vent connection to a non hazardous location on the outside away from any potential sources of ignition The vent piping must be connection size or larger and piped to a safe ar...

Page 3: ... to prevent vent blockage and minimize the chances for foreign material from collecting in the vent side of the regulator diaphragm 5 Use lubricants sparingly and with care to avoid exposing tacky surfaces to the gas stream Such surfaces could cause dirt accumulation on close clearance parts Use moly or silicone type lubricants Avoid the use of petroleum base types Lubricate the stem 24 the guide ...

Page 4: ...rough 5 under section To Remove Valves 2 Remove inlet orifice 28 as follows a Remove seal cap 1 back off adjusting screw 10 remove housing cover 5 and remove spring b Remove bottom plate 33 and then unscrew valve assembly by grasping 50h and turning 50e or 50i unscrews from 24 c Remove diaphragm case assembly by first opening union 60 and removing cap screws 34 d Remove cap screws 26 and remove in...

Page 5: ...necessary 7 Insert top spring button 12 Be sure it is nested correctly on the spring Also make sure that ball 13 is in place 8 Install housing cover 5 Be sure the lower end of adjusting screw 10 fits into the hole in button 12 9 Set adjusting screw 10 for desired outlet pressure Firmly tighten nut 11 and replace seal cap 1 Over Pressurization Protection Protection must be provided for the downstre...

Page 6: ...Set Adjustment Screw for Desired Outlet Pressure Inlet Remove Vent If Required 441 57S 60 Downstream Control Line A Control Connection Outlet N F D E C B Vent M Minimum Service Space Regulator F Face to Face in Body Type 2 Pipe 3 Pipe 4 Pipe 6 Pipe Screwed 10 Flanged ANSI 125 10 11 3 4 137 8 173 4 Flanged ANSI 250 101 2 121 2 141 2 185 8 Flanged ANSI 300 101 2 121 2 141 2 185 8 Flanged ANSI 600 11...

Page 7: ...odel D E M N 2 Pipe 6 24 5 7 3 Pipe 6 24 5 7 4 Pipe 91 2 25 5 8 6 Pipe 12 281 2 5 14 Outlet Nominal Pressure Spring Diaphragm Min to Max Color Size I D 3 to 6 psi Yellow 5 to 9 psi Gray 7 1 2 to 15 psi Blue 12 1 2 to 30 psi Red 5 all ranges 25 to 55 psi Brown 50 to 75 psi Black 70 to 100 psi Brown plus White White colored spring is nested within brown Spring Ranges Dimensions in Inches Installatio...

Page 8: ...ce Plug 090 16 361 01 and Steel Union Assembly 90 Nameplate 090 00 086 05 91 Nameplate round 090 16 086 00 92 Rd Hd Type U Drive Screw 903004 4 x 3 16 Lg 93 Rd Hd Machine Screw 914402 6 32 x 1 4 Lg 2 and 3 Models Illustration Part Number Description Number 22 Lower Diaphragm Plate 091 00 022 00 22a O Ring 5 8 x 3 4 902922 23 O Ring 11 16 x 7 8 934013 24 Diaphragm Connecting Screw 090 16 058 00 sta...

Page 9: ...e Assembly 1 3 4 brass trim Polyurethane 090 16 515 32 Red 65 75 Duro Valve Assembly 1 3 4 stainless steel trim 090 16 515 52 50 Polyurethane Red 65 75 Duro Valve Assembly 1 1 2 brass trim Polyurethane 090 16 515 33 Red 65 75 Duro Valve Assembly 1 1 2 stainless steel trim 090 16 515 53 Polyurethane Red 65 75 Duro 6 Models Illustration Part Number Description Number 22 Lower Diaphragm Plate 091 00 ...

Page 10: ...lamp Screw for 1 1 2 valve only 090 16 046 01 50h Male Valve Stem brass 090 16 016 01 Male Valve Stem stainless steel 090 16 016 02 4 Models Illustration Part Number Description Number Valve Assembly 3 brass trim Polyurethane Red 65 75 Duro 090 22 515 40 Valve Assembly 3 stainless steel trim Polyurethane 090 22 515 60 Red 65 75 Duro Valve Assembly 2 1 8 brass trim 50 Polyurethane Red 65 75 Duro 09...

Page 11: ...043 03 reduced valve only Adjustment Clamp Screw 50g Soc Hd Screw 5 16 18 x 1 Lg 903498 Adjustment Clamp Screw for 2 1 8 reduced valve only 903494 Male Valve Stem stainless steel 090 24 116 01 50h Male Valve Stem brass for 2 1 8 reduced valve only 090 24 116 10 Stem Extension stainless 090 24 062 04 50i Valve Stem Hex Extension stainless for 2 1 8 reduced valve only 090 16 062 11 Travel Stop for 4...

Page 12: ...ffective unless buyer notifies Seller in writing of any purported defect or nonconformance with thirty days after Buyer discovers or should have reasonably discovered such purported defect or nonconformance and d shall only extend to Buyer and not to any subsequent buyers or users of the Goods Buyer shall provide Seller access to the Goods as to which Buyer claims a purported defect or nonconforma...

Reviews: