background image

 

- 1 - 

 

 

 

 

 

 

 

USER MANUAL 

 

 

 

 

DPSKO-xx  

Dual axis planarity sensor with relay or open collector output 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for DPSKO Series

Page 1: ...1 USER MANUAL DPSKO xx Dual axis planarity sensor with relay or open collector output...

Page 2: ...rking principle pg 3 2 Technical features pg 4 3 Safety pg 5 4 Electrical connections pg 6 5 Calibration and setting using RS 232 port pg 8 6 Mounting pg 14 7 Disposal pg 15 8 Precautionary measures c...

Page 3: ...s an output X and Y planarity for two half axis each allowing DPSK to be used for auto levelling or other optional functions Zero setting can be achieved through a dedicated cable optional or through...

Page 4: ...xis half axis transistor 1 0 A 50 C Supply current max relay output 200 mA Supply current max transistor output 100 mA 2 1 1 Annotation 1 Relay and open collector outputs are protected using 1A built...

Page 5: ...polarity overvoltage B Planarity output relay short circuit overvoltage C Axis half axis output transistor short circuit overvoltage D Axis half axis output relay short circuit 3 2 Conformity DPSK con...

Page 6: ...st avoid improper cable bending traction twisting pressing or squeezing during machine operation Cable shall be chosen so to conform device specific application Supply 1 5 mm 2 cabling under 1 5 m in...

Page 7: ...ction AMP PIN 2 Rx RS232 Rx to PC connection AMP PIN 3 Tx RS232 Tx to PC connection AMP PIN 1 Gnd RS232 Gnd to PC connection Annotation 2 RS 232 levels are already shifted to allow direct communicatio...

Page 8: ...factory set Factory settings can be modified using RS 232 communication with any Hyperterminal like program Please refer to the following commands to set intervention ranges 5 2 1 MDEGX maximum allowe...

Page 9: ...s RS 232 settings are the following Communication 9600 bits s Data bit 8 Parity none Stop 1 Flow control none On power on DPSK sends through RS 232 the following info concerning the device device code...

Page 10: ...0 normally NOT OPERATING operates after X or Y switching point is reached 255 normally OPERATING gets not operating after X or Y switching point is reached FWAITX 1 1 255 Delay to deactivate X axis a...

Page 11: ...11 Example of the configuration using Windows HyperTerminal 1 COM port configuration 2 After power on DPSK sends through RS 232 the following info...

Page 12: ...gh RS 232 the following info Syntax error 4 Command MDEGX 20 to set the switching angle for X axis at 2 0 To set switching angle for X axis using MDEGX command please type desired angle value multipli...

Page 13: ...EGX to read the switching angle for X axis already set To read switching angle for X axis using MDEGX command please type desired angle value multiplied by ten to allow definition of decimal values of...

Page 14: ...14 6 Mounting...

Page 15: ...power transmitting lines 8 1 6 Do not spray pressurized water or cleaning liquids directly over the device 8 1 7 Do not break crack pierce or make holes on the device 8 2 Checks and maintenance If th...

Page 16: ...ary maintenance Extraordinary maintenance comprises every maintenance which is not listed in the installation guidelines or ordinary maintenance paragraph Extraordinary maintenance shall be carried ou...