- 10 -
=
And the desired value and pres <ENTER> key
RWAIT=12
<Enter>
Sets RWAIT to 1.2 seconds
If the user gives a parameter an
out-of-range
value or a
wrong
name “
Syntax error
”
will be printed on the screen.
In such a case the user shall press <ENTER>.
5.5 RS-232 parameters table
Parameters for RELAY OUTPUT
Parameter
Standard
Value
Description
CHGREL
255
[0,255]
Relay output setting: 0: normally NOT OPERATING; operates after X or Y
switching point is reached 255: normally OPERATING; gets not operating
after X or Y switching point is reached.
RWAIT
1
[1-255]
Delay to activate alarm, from 100 ms to 25.5 seconds
MDEGX
50
[1-200]
Maximum angle for X axis
MDEGY
50
[1-200]
Maximum angle for Y axis
FWAIT
1
[1-255]
Delay to deactivate alarm, from 100 ms to 25.5 seconds
ZERO
-
-
Zeroing
Parameters for OPEN COLLECTOR OUTPUT
Parameter
Standard
Value
Description
CHGOUT
255
[0,255]
Relay output setting: 0: normally NOT OPERATING; operates after X or Y
switching point is reached 255: normally OPERATING; gets not operating
after X or Y switching point is reached.
FWAITX
1
[1-255]
Delay to deactivate X-axis alarm from 100 ms to 25.5 s
FWAITY
1
[1-255]
Delay to deactivate Y-axis alarm from 100 ms to 25.5 s
RWAITX
1
[1-255]
Delay to activate X-axis alarm from 100 ms to 25.5 s
RWAITY
1
[1-255]
Delay to activate Y-axis alarm from 100 ms to 25.5 s
MXN
10
[1-200]
Maximum angle for X- half-axis
MXP
10
[1-200]
Maximum angle for X+ half-axis
MYN
10
[1-200]
Maximum angle for Y- half-axis
MYP
10
[1-200]
Maximum angle for Y+ half-axis
Parameters for Angle range Hysteresis setting (deactivates/activates alarm)
Parameter
Standard
Value
Description
ISTRELE
1
[0-200]
Angular Hysteresis for relay output (managed by MDEGX e MDEGY)
ISTSEMI
1
[1-200]
Angular Hysteresis for PNP output (managed by MXN, MXP, MYN e MYP)
Angular values for hysteresis setting (ISTRELE and ISTSEMI) are expressed in 0.1°. Angular
Hysteresis represents the minimum angle (over/under the switching point) able to activate/deactivate
alarm.