LAM71, Release 001_Revision 001
31
Low = 0
U < 1 V
High = 1 : U = operating voltage
–
1V
Variable
Description
Specification
w
Switching threshold
- 9999,999 ... + 9999,999
x
Switching range
x > 0 ; x > y
y
Switching hysteresis
y > 0
z
Switching state
z = 0 or 1
Query:
Q1 or Q2
Set:
Q1w x y z or Q2w x y z
Standard:
0.000 1.000 0.050 1
The LDS30 does not perform a plausibility check of Q1 or Q2 settings respectively.