Part Number: 1460105
REV: A
Relay Menu
Selecting Enter will advance to the following menu.
Arrow down to the next screen will be
Select the Alarm Relay (LOW, MID, HI, FAULT) that is to be configured using the down arrow. Once the
cursor is on the correct alarm relay, hold the magnet over Enter. The example LOW will be used. The
same operations can be used to set the MID, HI, or FAULT relays.
Select Enter
Select Enter
Using the Up and Down arrows the operator can change the ON delay time for the relay to actuate after the
alarm threshold has been exceeded. The time is measured in seconds (0-255). Once the correct time is
displayed select Enter to accept the new value. Then Exit the menu and proceed on to the next selection.
In this example the Low alarm relay will actuate 30 seconds after the Low set point is exceeded.
CALIBRATION
ALARM
* RELAY
* LOW
MID
HI
* FAULT
EXIT
* LOW
MID
HI
* ON DLY LOW 0
OFF DLY
ENERGIZED
EXIT
* ON DLY LOW 0 *
OFF DLY
ENERGIZED
EXIT
* ON DLY LOW 30
OFF DLY
ENERGIZED
EXIT