2) INSTALLATION
2.1)
Mounting and electrical connections
After opening the transparent unit door, also open the front panel by rotating the black lock to
UNLOCK.
Remove the 4 screws at the 4 corners of the box and remove the front part of the unit box.
Holes can now be drilled in the back of the box for wire passage.
We recommend you use an IP65 wire clamp at wire entrance to maintain the same protection
level as the unit.
Secure the back of the unit to the wall using the holes (D) or by the enclosed brakets.
Fig. 2.1 a) Control panel box
Dimensions (mm): A 470, B 426, C 380, D 312, E 128, F 148, G 14, H 125, I 75, L 50, M 48, N
98, O 41
Connect the tri-polar mains wire to the power supply terminal board (minimum 1.5mm
2
per pole) and secure it with the specific wire clamp.
Power the unit and, next, connect the red and black tipped faston wires to the 2 x 12 V 7
Ah max lead buffer battery power supply.