background image

 

 

9

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig 3

 Detector Field of View Plot 

 
The flame detector should be positioned at the perimeter of the room, pointing directly at the 
anticipated flame or at the centre of the area to be protected. If the detector cannot ‘see’ the whole 
of the area to be protected, one or more additional detectors may be required. 
 
The flame detector is not affected by normal light sources but should be positioned so that sunlight 
does not fall directly onto the viewing window.  
 
 
 

Detector Window Contamination 

It is important to keep the detector window clean and checks should be carried out at regular 
intervals – determine locally according to the type and degree of contamination encountered – to 
ensure optimal performance of the flame detector. Although the IR detectors can detect flames 
when the window is contaminated, there may be a reduction of sensitivity as shown in Table 1. 
 
 

Contamination 

Typical percentage of 
normal response 

Water spray 

75% 

Steam 

 

75%

Smoke 

 

75%

Oil film 

86% 

Salt water film 

86% 

Dry salt deposits 

86% 

Table 1 

IR Detector window contamination

 

UV/IR detectors are more susceptible to window contamination and must be kept clean. 

Connection Information

 

Centre line of detector 

 

0.4m² flame seen at 40m 

 

 

 

 

15°

30°

75°

-15°

 

-75°

 

-90°

 

0

 

25m

-45°

 

-60°

 

-30°

40m

90°

60°

45°

0.1m² flame seen at 25m 

Detector 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig 8 

Basic 2 Wire Connection Diagram

 

 
 
 
The simplest method of connecting the flame detector is in a 2-wire configuration as shown above. 
With a 24Vdc supply the current (

i

)

 drawn by a detector/detectors can be monitored to determine the 

detector status. The DIL switches within the detector can be set to produce different current values 
(

i

)

 to suit control systems.   

 
 
 

Detector Supply Current 

 @ 24Vdc 

DIL Switch Setting 

Normal 

Quiescent 

Current 

Alarm  

(Fire) 

Current 

 
 

 
 

 
 

 
 

Comment 

3mA 

9mA 

Lowest power configuration, RL1 only 

4mA 

20mA 

For 4-20mA systems, no relays 

8mA 

14mA 

Lowest power configuration & relays 

8mA 

20mA 

For 4-20mA systems & relays 

8mA 

 

       

 

28mA

1

1

1

1

Fire 

control 

panels

 

Table 4 

Detector Supply & Alarm Currents 

 
 
If the detector supply current falls below the normal quiescent current consumption then a fault is 
present. This could be simply an open circuit cable fault or a fault within the detector possibly due to 
the detector being taken over its rated temperature. 
Detectors can be connected in parallel increasing the overall quiescent current required. The alarm 
current signal will remain the same with the additional quiescent current drawn from other detectors.      
 

2

1

Control Unit 

(Supplied by others) 

Flame Detector 

Single pair cable, also see note 1 

i

+

+

24Vdc Normal 

(Break supply to reset

if detector set to latch) 

-

-

NOTE 1 
Screened cable should be used with one end
of the screen connected to earth. Also care
should be taken not to run the detector cable
next to power cables. 

Reviews: