SenseAir eSENSE II Installation Manual Download Page 3

 

 

 

 

 

Document 

IMA0121

  

Rev 

3

 

Page 
3 (4)

 

 

Electrical connections

  

The power supply 

has to be connected

 

to 

 

and 

 is considered as system 

ground. 

The same ground reference has to be used for

 

the eSENSE  unit and for the 

DDC/signal receiver.

   

 

PLEASE NOTE! 
The same ground reference has to be used for the 

eSENSE

  

unit and for the control system!

 

 

Terminal 

Function 

Electrical data 

Standard settings 

Settings of 

this sensor 

 

 

 

Power (+) 

 
 

Power 

ground (-) 

24 VAC/DC+   

(+-20%), 2W 

 

24 VAC/DC- 

 
 
 
System voltage 
reference 

 

OUT(1) 

 
 

OUT(2) 

 

Analogue 

output 1 (+) 

 

Analogue 

output 2 (+) 

 

0-10 VDC 

 
 

2,0…10,0 VDC or  

4,0 … 20,0 mA 

 

0,9…1,6 VDC or 

1.5 to 2,5 mA 

 

0 VDC or 0mA 

0-2000 ppm

 

CO

2

 

 
 
0-2000 ppm

 

CO

 
 
Status = ERROR 
 
 
Status = NOT 
READY 

 

Table I. Connections of the main terminal of 

eSENSE

 

 

 

 

 

Figure 4. The

 eSENSE II

 

PCB seen from the front and the back. The OUT2 jumper is in 

the default position (voltage) 

 

~

+

~

+