background image

 

 

 

 

 

Document 

IMA0123

  

Rev 

4

 

Page 
3 (4)

 

 

Electrical connections

  

 

The power supply 

has to be connected

 

to 

+~ 

and 

 is considered as system 

ground. 

The same ground reference has to be used for

 

the eSENSE unit and for the 

DDC/signal receiver.

   

 

PLEASE NOTE! The same ground reference has to be 
used for the 

eSENSE

 unit and for the control system!

 

 

Terminal 

Function 

Electrical data 

Remarks 

+~ 

 
 

 

Power (+) 

 
 

Power ground 

(-) 

24 VAC/DC+  (+-

20%), 2W 

 

24 VAC/DC- 

 
 
 
System voltage reference 

OUT1 

 
 

OUT2 

 

Analogue 

output 1 (+) 

 

Silences the 

acoustic alarm  

0-10 VDC 

 

 

0-2000 ppm

 

CO

2

 

 
A push on the push button 
silences the acoustic alarm for 30 
minutes. 

Table I. Connections of the main terminal of eSENSE

 

 

 

LED Colour

 

Electrical data 

Remarks 

Green 

0VDC 
 
10VDC 

 
 
Lit between 0-800 ppm CO

2

 

Yellow 

0VDC 
 
10VDC 

 
 
Lit between 800-1400 ppm CO

2

 

Red 

0VDC 
 
10VDC 

 
 
Lit above 1400 ppm CO

2

. Buzzer sounds. 

Table II. The LEDs

 

 

Self-diagnostics 

The  system  contains  complete  self-diagnostic  procedures  that  are  executed 
automatically when the sensor is in operation. Sensors with display show a 

wrench

 if 

an error is found. The wrench is shown during the first seconds after power up and if 
the measuring range is exceeded.  
 

Maintenance 

The 

eSENSE

  is  basically  maintenance  free  in  normal  environments  thanks  to  the 

built-in self-correcting 

ABC 

algorithm. Discuss your application with your distributor in 

order to get advice for a proper calibration strategy. 
 

PLEASE  NOTE!  The  sensor  accuracy  is  defined  at  continuous  operation  (at 
least 3 weeks after installation) 
 
Electronic products should be disposed of via a suitable recycling centre. 